17-11. Driving power recovery request (RPwr) and action restart request
(RAct)
(1) Driving power recovery request
How to request driving power recovery
The driving power recovery can be requested with any of the following methods:
Set the I/O parameter No. 44 (input selection function 014 = driving power restart input) to
1, and input ON edge for the input port No. 14.
Select Controller (C) from the PC software menu and execute Driving Power Recovery
Request (P).
Select Ctl (controller operation) on the Mode Selection screen of the Teaching Pedant
and execute RPwr (driving power recovery request).
Case where driving power recovery request is required
The driving power recovery request is required only in the following case:
Where the factor behind the driving power down occurs when the I/O parameter No. 44 is
set to 1 and the driving power recovery is attempted after the factor removal.
(2) Action restart request
How to request action restart
The action restart can be requested with any of the following methods:
Set the I/O parameter No. 35 to 1 (input selection function 005 = action restart signal),
and input ON edge for the input port No. 5.
Select Controller (C) from the PC software menu and execute action restart request (L).
Select Ctl (controller operation) on the Mode Selection screen of the Teaching Pendant
and execute RAct (action restart request).
Case where action restart request is required
The action restart request is required in any of the following cases:
Where the controller in auto run stops with the Deadman switch when the other
parameter No. 9 is set to 2 (Deadman SW recovery type = action continuation recovery
[only in auto run]) and recovery is attempted after the stop reset (action restart).
Where the controller in auto run makes an emergency stop when the other parameter No.
10 is set to 2 (emergency stop recovery type = action continuation recovery [only in auto
run]) and recovery is attempted after the emergency stop reset (action restart).
Where the safety gate is OPEN in auto run when the other parameter No. 11 is set to 2
(safety gate OPEN time recovery type = action continuation recovery [only in auto run])
and recovery is attempted after safety gate CLOSE (action restart).
Where the input port No. 6 OFF level is input (action temporary stop) in auto run when
the I/O parameter No. 36 is set to 1 (input selection function 006 = action temporary stop
signal) and recovery is attempted after the input port No. 6 ON level input (action restart).
* Where (1) overlaps (2) , it is required to execute the driving power recovery request first and
then the action restart request.