Owner manual

104
[3] Set parameters as shown below from now. Mode setting should be “Remote net [Ver. 1 mode].”
Parameters different from initial setting are as follows.
“Start I/O No”
・・・・・・・・・・・・
I/O address of master unit, 0080
“All connect account”
・・・・
Number of remote stations, 2
“Remote input (RX) Refresh device”
・・・・・・・・・
X100
Remote output (RY)
・・・・・・・・・・・・・・・・・・・・・・・・・
Y100
Remote register (RWr)
・・・・・・・・・・・・・・・・・・・・・・
D200
Remote register (RWr)
・・・・・・・・・・・・・・・・・・・・・・
D100
Special relay (SB)
・・・・・・・・・・・・・・・・・・・・・・・・・・・
SB80
Special register (SW)
・・・・・・・・・・・・・・・・・・・・・・・・
SW80
Install master station buffer
memory to an internal device
of the PLC-CPU.