COMPLIANCE
Agency File
UL916 – Energy Management Equipment
ZigBee Profile (Plover) 0x114B
FCC
ENVIRONMENTAL
Parameter Symbol Min Typ Max Units
Operating Temperature T
O
0 25 40 C
Storage Temperature T
-40 100 C
Relative Humidity RH 0 95 %
InteliSockets are for indoor use only.
PROTOCOL
InteliSockets use Ibis’ custom Plover profile for commands, acknowledgements, and reporting
of data.
DATA
InteliSockets report data typically every 15 seconds. Each report packet is comprised of socket
type, ZigBee channel, ZigBee hive (PANID), interval (seconds), voltage (RMS), frequency (Hz),
energy (watt-seconds), and power factor (fraction). From these data we can calculate
instantaneous power (watts) and current (amps).






· 
The InteliGateway appends additional information (IP, timestamp, location, etc.) before
uploading to the InteliNetwork. This allows any socket in the world to be located and
addressed individually.