A Guide to IBM System x Power Distribution Units (PDU) International Version IEC320 C19 6 1 5 L1 LAN 12 R N 4 L2 2 L3 3 IEC320 C20 G LAN Ultra PDU 2 A B 1 C F 9 8 E 6 5 4 10 Breaker Amperage 11 1 12 3 10 10A 11 10A 12 10A C13 C13 C13 9 16A 8 16A 7 16A C19 C19 C19 Outlet Type 7 D Outlet Number 2 Outlet Amperage 20A 20A 20A 20A 20A 20A 6 16A 5 16A 4 16A C19 C19 C19 20A 20A 20A 3 16A 2 16A 1 16A C19 C19 C19 L2 L1 N L3 E Color Indicates Outlet Grouping Per Phas
A Guide To IBM System x Power Distribution Units (PDU) - International Revision History 1.0 – December 17, 2009 1.0.1 – March 5, 2010 1.0.2 – March 31, 2010 1.3.0 – April 21, 2010 1.3.1 – May 21, 2010 1.3.2 – June 10, 2010 1.3.3 – July 20, 2010 2.0.0 – October 20, 2010 2.1.0 – January 26, 2011 2.1.1 – February 8, 2011 2.1.2 – March 1, 2011 2.1.3 – March 15, 2011 2.2.0 – August 12, 2011 2.3.0 – June 20, 2012 2.3.1 – February 03, 2014 2.3.
A Guide To IBM System x Power Distribution Units (PDU) - International Table of Contents TABLE OF CONTENTS ........................................................................................................................................................... 3 INTRODUCTION ................................................................................................................................................................... 5 HOW TO USE THIS GUIDE..............................................
A Guide To IBM System x Power Distribution Units (PDU) - International FRONT END PDU MOUNT OPTIONS.............................................................................................................................................. 35 ENTERPRISE SHALLOW PDU MOUNT OPTIONS................................................................................................................................ 39 ENTERPRISE DEEP PDU MOUNT OPTIONS...................................................................
A Guide To IBM System x Power Distribution Units (PDU) - International Introduction Only IBM System x Power Distribution Units (PDUs) that are currently marketed in internationally are included in this guide. The intent of this guide is to provide PDU information needed in planning power requirements. This guide is best used in softcopy form, since it contains hyperlinks for navigation. This document can still be used in hardcopy as reference only.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Basic PDUs (Non-monitored) IBM Basic PDUs do not have the ability to collect power statistics or control the outlets remotely.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Universal Rack PDU 39Y8952, 39Y8953, 39Y8954, 39Y8955, 39Y8956, 39Y8957, 39Y8958, 39Y8959, 39Y8960, 39Y8961, 39Y8962 Internal Circuit Layout Breaker Amperage Outlet Number 15A 7 6 5 4 3 2 1 10A 10A 10A 10A 10A 10A 10A C13 C13 C13 C13 C13 C13 C13 Outlet Amperage Outlet Type Input Line Cords By PDU Model See Page 22 for 39Y8952 Line Cord Information See Page 22 for 39Y8953 Line Cord Information See Page 22 for 39Y8954 Line Cor
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Front End PDU 39Y8934, 39Y8935, 39Y8938, 39Y8937 Internal Circuit Layout Front Panel 20A 20A Fuse Amperage 20A 3 16A 2 16A 1 16A C19 C19 C19 Outlet Amperage Outlet Type Back Panel Input Line Cords By PDU Model – Line cord comes with the PDU 39Y8934 – IBM DPI IEC 309 P+N+G (2.5m) line cord 32A / 220-240VAC Single Phase 39Y8936 – IBM DPI KSC 8305 30A (2.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM DPI® Enterprise PDU – C13 39Y8941 Internal Circuit Layout 20A 2 1 3 Back Panel 4 Front Panel Outlet Number 20A 12 11 10 9 10A 10A 10A 10A Outlet Amperage C13 C19 C13 C13 C13 Outlet Type 20A 20A Breaker Amperage 20A 6 5 20A 8 7 6 5 10A 10A 10A 10A C13 C13 C13 C13 4 3 2 1 10A 10A 10A 10A C13 C13 C13 C13 Input Line Cords 40K9611 – IBM DPI IEC-309 3P+N+G (4.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM DPI Enterprise PDU 39Y8948 Internal Circuit Layout 2 Outlet Number 1 20A 6 16A C19 20A 5 16A C19 Outlet Type 4 3 Back Panel 20A Front Panel Outlet Amperage Breaker Amperage 20A 20A 20A 4 16A 3 16A C19 2 16A 1 16A C19 C19 C19 6 Color Indicates Outlet Grouping Per Phase On Three Phase Model 5 Input Line Cords 40K9611 – IBM DPI IEC-309 3P+N+G (4.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM DPI Ultra Density Enterprise PDU 71762NX Internal Circuit Layout 10A Max Group Amperage 10 10A 11 10A 12 10A C13 C13 C13 20A 20A 20A 9 16A 8 16A 7 16A C19 C19 C19 20A 20A 20A 6 16A 5 16A 4 16A C19 C19 C19 20A 20A 20A 3 16A 2 16A 1 16A C19 C19 C19 Outlet Amperage Outlet Type 12 11 Back Panel 6 5 4 Front Panel 10 3 2 1 Outlet Number Breaker Amperage 9 8 7 D E F C 1 B A 2 Color Indicates Outlet Groupin
A Guide To IBM System x Power Distribution Units (PDU) - International IBM 0U 24 C13 PDU 46M4122 & 46M4131 Outlet Type Outlet Number C13 C13 C13 C13 C13 C13 C13 C13 10A 10A 10A 10A 10A 10A 10A 10A 4 3 2 1 20A 20A 8 7 6 5 C13 C13 C19 C13 C13 10A 10A 10A 10A C13 C13 C19 C13 C13 10A 10A 10A 10A 16 15 14 13 12 11 10 9 C13 C13 C19 C13 C13 10A 10A 10A 10A Color Indicates Outlet Grouping Per Phase 20 19 18 17 20A 24 23 22 21 10A 10A 10A 10A C13 C13 C19 C13 C13 Outlet Amperage Breaker Amperage
A Guide To IBM System x Power Distribution Units (PDU) - International IBM 0U 12 C19/12 C13 PDU 46M4143 Outlet Type C19 C19 C13 C13 16A 16A 10A 10A 4 3 2 1 20A 20A 20A C19 C19 C13 C13 16A 16A 10A 10A 12 11 10 9 20A C19 C19 C13 C13 C19 C19 C13 C13 16A 16A 10A 10A 16 15 14 13 20A 16A 16A 10A 10A C19 C19 C13 C13 16A 16A 10A 10A 20 19 18 17 20A Outlet Number 8 7 6 5 C19 C19 C13 C13 16A 16A 10A 10A Color Indicates Outlet Grouping Per Phase 24 23 22 21 Outlet Amperage Breaker Amperage Input L
A Guide To IBM System x Power Distribution Units (PDU) - International IBM 1U Higher Voltage DC PDU 44T0966 Internal Circuit Layout Back Panel Front Panel Outlet Number Breaker Amperage Outlet Amperage 15A 1 15A RF-203P 15A 2 15A RF-203P Outlet Type 15A RF-203P 15A 3 15A 4 15A 15A 5 15A RF-203P 15A 6 15A RF-203P RF-203P Note: RF-203P outlet refers to Rong Feng RF-203P DC outlet. Input Line Cords Attached 90A DC line cord 90A@240-380VDC (4.3m) line cord hardwired (i.e.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Monitored PDUs IBM Monitored PDUs collect power statistics that can be viewed through PDUs web interface or IBM Active Energy Manager. These PDUs do not have the ability to control the outlets remotely. For IBM PDUs that have the ability to control outlets see the “IBM Switched and Monitored PDUs” section on page 16.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM DPI Enterprise PDU+ - C13 39M2816 Internal Circuit Layout LAN 20A R 1 2 1 2 3 5 4 Back Panel Front Panel Outlet Number 6 20A 12 11 10 9 10A 10A 10A 10A Outlet Amperage C13 C19 C13 C13 C13 Outlet Type 20A 20A Breaker Amperage 20A 20A 8 7 6 5 10A 10A 10A 10A C13 C13 C13 C13 4 3 2 1 10A 10A 10A 10A C13 C13 C13 C13 Input Line Cords 40K9611 – IBM DPI IEC-309 3P+N+G (4.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Switched and Monitored PDUs IBM Switched and Monitored PDUs collect power statistics and have the ability to control outlets remotely via the PDUs web interface or IBM Active Energy Manager.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM 1U 12 C13 Switched and Monitored PDU 46M4004 Internal Circuit Layout LAN 1 2 3 4 5 Back Panel Front Panel 12 11 10 9 20A 6 Outlet Number 20A Outlet Switch Relay 20A 10A 10A 10A 10A Outlet Amperage C13 C19 C13 C13 C13 Outlet Type 20A Breaker Amperage 20A 20A 8 7 6 5 10A 10A 10A 10A C13 C13 C13 C13 4 3 2 1 10A 10A 10A 10A C13 C13 C13 C13 B C A D E F 2 1 Color Indicates Outlet Grouping Per Phase On Three
A Guide To IBM System x Power Distribution Units (PDU) - International IBM 1U 9 C19 / 3 C13 Switched and Monitored PDU 46M4002 Internal Circuit Layout Group Amperage 10A Max LAN 10 10A 11 10A 12 10A Outlet Amperage C13 C13 C13 Outlet Type 10 Front Panel Back Panel 11 12 Outlet Number Outlet Switch Relay Breaker Amperage B C A D E F 2 9 16A 8 16A 7 16A C19 C19 C19 20A 20A 20A 6 16A 5 16A 4 16A C19 C19 C19 20A 20A 20A 3 16A 2 16A 1 16A C19 C19 C19 1 20A 20A 20A Color Indicates Out
A Guide To IBM System x Power Distribution Units (PDU) - International IBM 0U 24 C13U Switched and Monitored PDU 46M4119 Outlet Type Outlet Number C13 C13 C13 C13 C13 C13 C13 C13 10A 10A 10A 10A 10A 10A 10A 10A 4 3 2 1 20A 20A 8 7 6 5 C13 C13 C19 C13 C13 10A 10A 10A 10A C13 C13 C19 C13 C13 10A 10A 10A 10A 16 15 14 13 12 11 10 9 C13 C13 C19 C13 C13 10A 10A 10A 10A Color Indicates Outlet Grouping Per Phase 20 19 18 17 20A 24 23 22 21 10A 10A 10A 10A C13 C13 C19 C13 C13 Outlet Amperage Bre
A Guide To IBM System x Power Distribution Units (PDU) - International IBM 0U 12 C19/12 C13 Switched and Monitored PDU 46M4137 Outlet Type C19 C19 C13 C13 16A 16A 10A 10A 4 3 2 1 20A 20A 20A C19 C19 C13 C13 16A 16A 10A 10A 12 11 10 9 20A C19 C19 C13 C13 C19 C19 C13 C13 16A 16A 10A 10A 16 15 14 13 20A 16A 16A 10A 10A C19 C19 C13 C13 16A 16A 10A 10A 20 19 18 17 20A Outlet Number 8 7 6 5 C19 C19 C13 C13 16A 16A 10A 10A Color Indicates Outlet Grouping Per Phase 24 23 22 21 Outlet Amperage Bre
A Guide To IBM System x Power Distribution Units (PDU) - International Line Cords and Plugs Universal Rack PDU (39Y8952) 230VAC (CEE7-VII Europe) 39M5281 – C19 to CEE7-VII Europe (1.8m) @ 230VAC Single Phase 39M5282 – C19 to CEE7-VII Europe (2.5m) @ 230VAC Single Phase 39M5283 – C19 to CEE7-VII Europe (4.3m) @ 230VAC Single Phase Used with: 39Y8952 – Universal Rack PDU Female End Male End Universal Rack PDU (39Y8953) 230VAC (Denmark/Switz. IEC 309 P+N+G) 39M5321 – C19 to Denmark IEC 309 P+N+G (1.
A Guide To IBM System x Power Distribution Units (PDU) - International Universal Rack PDU (39Y8955) 230VAC (Italy CEI 23-16) 39M5297 – C19 to Italy CEI 23-16 (1.8m) @ 230VAC Single Phase 39M5298 – C19 to Italy CEI 23-16 (2.5m) @ 230VAC Single Phase 39M5299 – C19 to Italy CEI 23-16 (4.3m) @ 230VAC Single Phase Used with: 39Y8955 – Universal Rack PDU Female End Male End Universal Rack PDU (39Y8956) 220-250VAC (South Africa SABS 164) 39M5290 – C19 to South Africa SABS 164 (2.
A Guide To IBM System x Power Distribution Units (PDU) - International Universal Rack PDU (39Y8958) 230-240VAC (AUS/NZ 3112 Australia/NZ) 39M5329 – C19 to AUS/NZ 3112 Australia/NZ (1.8m) @ 230-240VAC Single Phase 39M5330 – C19 to AUS/NZ 3112 Australia/NZ (2.5m) @ 230-240VAC Single Phase 39M5331 – C19 to AUS/NZ 3112 Australia/NZ (4.3m) @ 230-240VAC Single Phase Used with: 39Y8958 – Universal Rack PDU Female End Male End Universal Rack PDU (39Y8959) 220VAC (China GB 2099.1) 39M5353 – C19 to China GB 2099.
A Guide To IBM System x Power Distribution Units (PDU) - International Universal Rack PDU (39Y8961) 230VAC (India IS 6538) 39M5444 – C19 to India IS 6538 (1.8m) @ 230VAC Single Phase 39M5445 – C19 to India IS 6538 (2.5m) @ 230VAC Single Phase 39M5446 – C19 to India IS 6538 (4.3m) @ 230VAC Single Phase Used with: 39Y8961 – Universal Rack PDU Female End Male End Universal Rack PDU (39Y8962) 220VAC (Argentina IRAM 2073) 39M5341 – C19 to Argentina IRAM 2073 (1.
A Guide To IBM System x Power Distribution Units (PDU) - International Front End (39Y8934) 220-240VAC / 32A Cord (IEC 309 P+N+G) IEC 309 P+N+G (2.5m) - 32A 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin & Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
A Guide To IBM System x Power Distribution Units (PDU) - International Front End (39Y8936) 220VAC / 30A Cord (KSC 8305 30A) P+N+G (Shin Ju P/N SJ-P3302) Korea connector Note that this is not the same cord as the 40K9618 cord. PDU line cord connector pin out is different. Used with: 39Y8936 - Front End PDU Female End L N Male End L G L 220V 220V N N G G EQUIP. GR.
A Guide To IBM System x Power Distribution Units (PDU) - International 40K9611 - IBM DPI 32A Cord (IEC 309 3P+N+G) IEC-309 3P+N+G (4.3m) 32A, 3P5W plug (Type 532P6W) 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin & Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
A Guide To IBM System x Power Distribution Units (PDU) - International 40K9612 - IBM DPI 32A Cord (IEC 309 P+N+G) IEC 309 P+N+G (4.3m) - 32A / 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin & Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
A Guide To IBM System x Power Distribution Units (PDU) - International 40K9617 – IBM DPI 32A Cord (AUS/NZ 3112 32A) P+N+G (PDL P/N 56P332) Australia/New Zealand connector Used with: 46M4002 – 1U 9 C19 / 3 C13 Switched and Monitored 46M4004 – 1U 12 C13 Switched and Monitored 71762MX – DPI Ultra Density Enterprise PDU+ 71762NX – DPI Ultra Density Enterprise PDU Female Sleeve 39M2816 – DPI Enterprise PDU+ (C13) 39Y8941 – DPI Enterprise PDU (C13) 39Y8948 – DPI Enterprise PDU (C19) Male Pin L 230V L N N L
A Guide To IBM System x Power Distribution Units (PDU) - International Attached 16A 3ph Cord (IEC309 3P+N+G) IEC-309 3P+N+G 3.0 meter 16A, 3P5W plug (Type 516P6W) 32A (32A / Phase) 380-415VAC Three Phase Wye 48A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin & Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
A Guide To IBM System x Power Distribution Units (PDU) - International Attached 32A 3ph Cord (IEC309 3P+N+G) IEC-309 3P+N+G 3.0 meter 32A, 3P5W plug (Type 532P6W) 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin & Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
A Guide To IBM System x Power Distribution Units (PDU) - International PDU Mount Options This section provides brief information on mounting options for the PDUs covered in this guide. For more detailed information on mounting options, refer to the PDU in questions installation manual. See IBM PDU Installation Manuals section on page 62 for links to IBM PDU installation manuals. Universal PDU Mount Options Hardware is included for both EIA (U space) mounting and side pocket mounting.
A Guide To IBM System x Power Distribution Units (PDU) - International Supported: 39Y8952 – Universal Rack PDU 39Y8953 – Universal Rack PDU 39Y8954 – Universal Rack PDU 39Y8955 – Universal Rack PDU 39Y8956 – Universal Rack PDU 39Y8957 – Universal Rack PDU 39Y8958 – Universal Rack PDU 39Y8959 – Universal Rack PDU 39Y8960 – Universal Rack PDU 39Y8961 – Universal Rack PDU 39Y8962 – Universal Rack PDU Mounting In U Space The horizontal mounting bracket, which ships with the IBM Universal Rack PDU, will need t
A Guide To IBM System x Power Distribution Units (PDU) - International Front End PDU Mount Options Units come with side wall mounting hardware only; however, Front End PDUs can be mounted in the EIA (U) space using the rack PDU hardware. Front End PDUs only support reconfigured shipment in side panel. Hardware is included for both EIA mounting and side of rack mounting. You must remove any horizontally-mounted Front End PDUs from the EIA mounting space before you relocate your rack cabinet.
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 39Y8934 – Front End PDU 39Y8935 – Front End PDU 39Y8936 – Front End PDU 39Y8937 – Front End PDU Mounting In IBM Enterprise Rack (9308 & 1410) & IBM Enterprise V2 Rack (9363) Rear Zero Pocket – Option 1 The horizontal-mounting bracket, which ships with the IBM Front End PDU, will need to be used for this installation option. Line cord will be routed directly out the back of the rack.
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 39Y8934 – Front End PDU 39Y8935 – Front End PDU 39Y8936 – Front End PDU 39Y8937 – Front End PDU Mounting In IBM Enterprise Rack (9308 & 1410) & IBM Enterprise V2 Rack (9363) Rear Zero Pocket – Option 2 The horizontal-mounting bracket, which ships with the IBM Front End PDU, will need to be used for this installation option.
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 39Y8934 – Front End PDU 39Y8935 – Front End PDU 39Y8936 – Front End PDU 39Y8937 – Front End PDU Mounting In U Space The horizontal-mounting bracket, which ships with the IBM Front End PDU, will need to be used for this installation option.
A Guide To IBM System x Power Distribution Units (PDU) - International Enterprise Shallow PDU Mount Options Hardware is included for EIA (U space) mounting, side of rack, and side pocket mounting. Only sided of rack and side pocket mounting installation is approved for reconfigured shipment in an IBM rack. Horizontal installation of a PDU is not supported during relocation or shipping of a rack cabinet.
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 39Y8941 – DPI Enterprise PDU (C13) 39Y8948 – Enterprise PDU (C19) Mounting In U Space The horizontal mounting brackets, which ships with the IBM Enterprise PDUs, will need to be used for this installation option.
A Guide To IBM System x Power Distribution Units (PDU) - International Enterprise Deep PDU Mount Options Hardware is included for EIA mounting (U space), side of rack, and side pocket mounting; only sided of rack and side pocket mounting installation is approved for reconfigured shipment in an IBM rack. Horizontal installation of a PDU is not supported during relocation or shipping of a rack cabinet.
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 39M2816 – DPI Enterprise PDU+ (C13) 71762MX – Ultra Density Enterprise PDU+ 71762NX – Ultra Density Enterprise PDU Mounting In U Space The horizontal mounting brackets, which ships with the IBM Switched PDUs, will need to be used for this installation option.
A Guide To IBM System x Power Distribution Units (PDU) - International Switched PDU Mount Options Hardware is included for EIA mounting (U space), side of rack, and side pocket mounting; only sided of rack and side pocket mounting installation is approved for reconfigured shipment in an IBM rack. Horizontal installation of a PDU is not supported during relocation or shipping of a rack cabinet. You must remove any horizontally mounted PDUs from the EIA mounting space before you relocate the rack cabinet.
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 46M4002 – 1U 9 C19 / 3 C13 Switched and Monitored 46M4004 – 1U 12 C13 Switched and Monitored Mounting In U Space The horizontal mounting brackets, which ships with the IBM Switched PDUs, will need to be used for this installation option.
A Guide To IBM System x Power Distribution Units (PDU) - International Zero U PDU Mount Options Supported with: 46M4119 – 0U 24 C13U Switched and Monitored 46M4122 – 0U 24 C13 Basic PDU 46M4131 – 0U 24 C13 Basic PDU 46M4137 – 0U 12 C19/12 C13 Switched and Monitored 46M4143 – 0U 12 C19/12 C13 Basic PDU Mounting In the Back of a IBM 42U Standard Rack (9307 & 9956) P a g e | 45 © IBM Corporation 2012
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 46M4119 – 0U 24 C13U Switched and Monitored 46M4122 – 0U 24 C13 Basic PDU 46M4131 – 0U 24 C13 Basic PDU 46M4137 – 0U 12 C19/12 C13 Switched and Monitored 46M4143 – 0U 12 C19/12 C13 Basic PDU Mounting In IBM Enterprise Rack (9308 & 1410) & IBM Enterprise V2 Rack (9363) Rear P a g e | 46 © IBM Corporation 2012
A Guide To IBM System x Power Distribution Units (PDU) - International Supported with: 46M4119 – 0U 24 C13U Switched and Monitored 46M4122 – 0U 24 C13 Basic PDU 46M4131 – 0U 24 C13 Basic PDU 46M4137 – 0U 12 C19/12 C13 Switched and Monitored 46M4143 – 0U 12 C19/12 C13 Basic PDU Mounting In the Back of IBM Racks With Integrated PDU Mounting Keyholes (9362, 9361, 9360) P a g e | 47 © IBM Corporation 2012
A Guide To IBM System x Power Distribution Units (PDU) - International IBM System x Rack Types IBM DPI PDUs are part of the IBM family of rack-based products. They are designed to easily install and work within IBM System x rack offerings. To gain a better understanding of the IBM System x rack family of products and the benefits they offer, please browse the IBM System x “Rack and Power Infrastructure Portfolio” Web site at http://www03.ibm.com/systems/x/hardware/options/index.html.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Enterprise Rack (42U) Installation Options The IBM Enterprise Rack is the premier IBM rack, offering four deep side bays that enable the greatest variety of side bay mounting options. This flexibility is one of the major benefits of choosing this rack. Using all the available space in the side bays of this rack enables customers to install up to 84 outlets in this rack without sacrificing any valuable “U” space.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Enterprise Rack Side Bays The depth of the IBM Enterprise Rack side bays allows the IBM System x PDUs to be nested side by side for large configurations PDUs. Here are a few examples of the supported PDU installations for the IBM Enterprise Rack. Note: Rack PDU in the following diagrams refers to the Universal Rack PDU.
A Guide To IBM System x Power Distribution Units (PDU) - International Standard Rack (47U) Installation Options This entry rack offers six side panel bay mounting locations. While it has more side bays than the Enterprise Rack, the Standard Rack's bays are less deep and do not allow the variety of mounting options of the Enterprise Rack. Even so, customers can install up to 56 outlets in the Standard Rack without sacrificing any "U" space.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Standard Rack Side Bay Here are some examples of the supported PDU mounting configurations in a single IBM Standard Rack side bay. Note: Rack PDU in the following diagrams refers to the Universal Rack PDU.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Standard Rack (42U) Installation Options This entry rack offers six side panel bay mounting locations. While it has more side bays than the Enterprise Rack, the Standard Rack's bays are less deep and do not allow the variety of mounting options of the Enterprise Rack. Even so, customers can install up to 56 outlets in the Standard Rack without sacrificing any "U" space.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM Standard Rack (25U) Installation Options This entry rack offers two side panel bay mounting locations. Here is graphical depiction of the side bays of the Standard Rack along with a lettering and numbering guide. It is important to note that the Standard Rack bays are not deep enough to accommodate two Enterprise or Ultra Density Enterprise PDUs in one bay.
A Guide To IBM System x Power Distribution Units (PDU) - International Reference Material IBM Flex System Enterprise Chassis Label Rating Chassis Flex Enterprise Flex Enterprise Power Supply Wattage 2500W 2100W Power Supplies Standard 2 2 Power Supplies Max 6 6 100-127VAC Rating - 200-240VAC Rating 13.85A / Supply 11.8A / Supply See “IBM Flex System Enterprise Chassis Power Guide” for further details on IBM Flex System Power: http://www.ibm.com/support/techdocs/atsmastr.
A Guide To IBM System x Power Distribution Units (PDU) - International IBM System x Server Label Rating Server x3100 (4348) x3100 M3 (4253) x3100 M4 (2582) x3100 M4 (2582) x3105 (4347) x3200 (4362, 4363) x3200 (4362, 4363) x3200 M2 (4367, 4368) x3200 M2 (4367, 4368) x3200 M2 (9234) x3200 M2 (9234) x3200 M3 (7327, 7328) x3200 M3 (7327, 7328) x3250 (4364, 4365) x3250 M2 (4190, 4194) x3250 M3 (4251, 4252) x3250 M4 (2583) x3250 M4 (2583) x3250 M5 (5458) x3350 (4192, 4193) x3250 M5 (5458) x3250 M5 (5458) x3300
A Guide To IBM System x Power Distribution Units (PDU) - International IBM System x Server Label Rating – Continued Server x3650 M2 (7838) x3650 M2 (7947) x3650 M3 (7945) x3650 M3 (7945) x3650 M4 (7915) x3650 M4 (7915) x3650 M4 (7915) x3650 M4 BD (5466) x3650 M4 BD (5466) x3650 M4 HD (5460) x3650 M4 HD (5460) x3650 M4 HD (5460) x3655 (7985) x3690 X5 (7147, 7148) x3690 X5 (7147, 7148) x3750 M4 (8722) x3750 M4 (8722) x3755 (8877, 7163) 3755 M3 (7164) 3755 M3 (7164) x3800 (8866) x3850 (8863, 8864) x3850/395
A Guide To IBM System x Power Distribution Units (PDU) - International IBM iDataPlex Chassis Label Rating Chassis Slot Configuration Power Supply Wattage Number Power Supplies Standard Max 2U Flex Chassis (7831, 6385) 2 Planars 900W High Efficiency 1 1 2U Flex Chassis (7831, 6385) 1 Planar with I/O Tray 900W High Efficiency 1 1 2U Flex Chassis (7381, 6385) 1 Planar with Storage Tray 900W High Efficiency 1 1 900W High Efficiency 1 1 3U Storage Chassis (7834, 6386) Chassis Rating 100VA
A Guide To IBM System x Power Distribution Units (PDU) - International IBM iDataPlex Chassis Label Rating – Continued Chassis Slot Configuration Power Supply Wattage Number Power Supplies Standard Max 2U Flex Chassis (7831, 6385) 2 Planars Dual 750W Power Supply 2 2 2U Flex Chassis (7831, 6385) 1 Planar with I/O Tray Dual 750W Power Supply 2 2 2U Flex Chassis (7381, 6385) 1 Planar with Storage Tray Dual 750W Power Supply 2 2 Dual 750W Power Supply 2 2 3U Storage Chassis (7834, 6386)
A Guide To IBM System x Power Distribution Units (PDU) - International IEC 309 Pin & Sleeve Plug Decode 4 60 Pin Configuration Amperage 3 - 2 Pole + G 4 - 3 Pole + G 5 – 3 Pole + N + G 20 30 32 60 63 100 R 9 Device Type Polarization Environmental Rating P - Plug C - Connector R - Receptacle Clock Position Of Female B - Inlet · o IEC309 3P+G Plug o 60amp/250V three-phase Hubbell Connector listing Voltage Rating Yellow 100V - 130V Orange 125V/250V Blue 200V - 250V Gray 277V Red 380V
A Guide To IBM System x Power Distribution Units (PDU) - International IEC 320 Connectors Name C5 – Female C6 – Male C7 – Female C8 – Male C13 – Female C14 – Male Connector AMP Rating 2.5A 2.
A Guide To IBM System x Power Distribution Units (PDU) - International 16A Three Phase Wye Power Calculations IA = IB = IC = IL = IF = 16A PF = EFY x IFY x pf (W) PTOTAL = 3 x PF = 3 x EL/√3 x IF x pf = √3 x EL x IL x pf = √3 x 380VAC x 16A x 1 = 10530W IA A EF=220VAC EL=380VAC B EAN = EBN = ECN = EF = EL √3 = 380VAC √3 IF EL=380VAC N IB EL=380VAC = 220VAC C IC IBM PDU Installation Manuals Rack, PDU, UPS, and KVM Product Publications Quick Reference http://www.ibm.