User Guide
Selectable Time Ranges
• Timing range multipliers x0.1, x1, x10, or x100
• Timing in Minutes or Seconds
(The example shown is set for “seconds” and the
multiplier is x1).
Timing Adjustment
• The time delay is adjusted by closing any combination
of 10 binary code switches
• Transfer a switch to the ON position then add all the
ON switch values for the total time delay.
(The example shown is set for 171 seconds).
Programming for Single Time Delays
(DOM, DOB, Interval, and Single Shot)
Setting the Mode of Operation
Mode of Operation A B C
DELAY ON MAKE OFF OFF OFF
DELAY ON BREAK OFF OFF ON
INTERVAL OFF ON OFF
SINGLE SHOT OFF ON ON
DOM-DOB
REPEAT CYCLE
See Page 10
6