7. Auxiliary Delay ON – (0-30 minutes) – Set the delay time in minutes for
auxiliary heat to be locked out after a call for second stage. This extra
savings feature is used to temporarily lock out auxiliary heat devices,
allowing just heat pump to try to satisfy heat call.
Press the up or down button to select.
Press the right button to advance to the next screen.
8. Lockout (0-8°, NITE, COOL-HEAT) – Select the number of degrees set
temperature can be changed during keypad lockout or select to lockout
during NITE period only. COOL-HEAT lockout allows adjustment of the set
temperatures to the maximum heat set temperature selected in Step 9 and
minimum cool set temperature selected in Step 10.
Note: The mode cannot be changed when the thermostat is locked.
Press the up or down button to select.
Press the right button to advance to the next screen.
9. Maximum Heat Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed.
Press the up or down button to select.
Press the right button to advance to the next screen.
10. Minimum Cool Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed.
Press the up or down button to select.
Press the right button to advance to the next screen.