6. Air Distribution System
Forairflowdata(blowerperformancedata,blowerspeedtapsettings,etc.)seetheTechni-
calData Sheetattachedto the unit..
Ductwork
Ductwork Insulation
Itisrecommendedthat ductworkinstalledoutdoorshaveaminimumof2" (51mm)offiber-
glassinsulationandbe coveredby aweatherproofvapor barrierthat isprotectedagainst
damage.Caulkingandflashings,or othermeansadequatetoprovidea permanentweath-
er seal,must be used.
Itisrecemmendedthatductworkinstalledin atticsorotherareasexposedtooutdoortem-
peratureshaveaminimumof 2" (51ram)fiberglassinsulationand havean indoortypeva-
por barrier.
Ductwork Connections
Theuseof flexible, non-combustibleconnectorsbetweenmaintrunk ductsand supply
and returnair plenumsis recommendedto minimizevibrationtransmission.
NOTE: Connectsupplyand returnair plenumsto unitin a mannerthatwill allowthe topof
the unitto be removedwithoutremovingplenums.PlenumsMUSTbe individuallysealed
to unitcasing.DuctsMUST be terminatedinsidestructure.
Filters
All returnair MUSTpassthrough a fieldsuppliedfilterbefore enteringthe unit.If used,an
electronicair cleaner MUSTbe installed in the return air ductwork. Minimum recom-
mendedfilter areasare listed in FIGURE16 and arebasedon a velocityof 300 ftfmin
(12m/s) for disposablefiltersand 500 ff/min(2.54m/s)for washablehighvelocityfilters.
CAUTION
NOTE:Thetotal heatgain ofthestructuretobe conditionedas expressedintotal Btuihr
should be calculatedby manufacturer's methodor in accordancewith"A.S.H.R.A.E
Guide"or"Manual J - LoadCalculations"publishedbytheAir ConditioningContractorsof
America. Thetotal heatgaincalculatedshouldbe equaltoor lessthan the coolingcapac-
ityoutput basedon D.O.E.test procedures,steadystate efficiencytimes input.
Ductwork,supplyregisters,and returnair grillesMUST be designedand sizedto handle
the unit'scoolingair volume requirements,tf the unitis connectedtoan existingsystem,
theductworkMUSTbecheckedtomakesureitis adequate.Extrarunsorlargerductsizes
mayhaveto be installed.
Maximumrecemmendedvelocityintrunkductsis1000feetperminute(5.08m/s).Velocity
in branchesshouldnot exceed800feet perminute(4.06m/s).Refertothe TechnicaIData
Labelon the unit forunit air volumerequirementsand systemsizing recommendations.
NOTE:Ductworksizingaffectstemperatureriseand coolingtemperaturedifferential.Be
sureto properlysizeductworkto the capacityand airflowcharacteristicsof your unit.Fail-
ureto doso canaffectlimitcontrols,compressors,motors,andother componentsandwill
leadto prematurefailure of components. Thiswillalso adversely affectday to dayunit
performance.
FlexibleDuctKitsareavailablefrom yoursupplierto effectpropersizingand installationto
MobileHomesandother standardconstruction..
Referto unitratingplatefor properElectricHeatAccessorysizing andsee the Tempera-
tureRiseChecksectionintheElectricHeatAccessorylnstallaUonSectionofthismanuaL Do NOT operate the unit without all filters in place.
FIGURE 16 Recommended Filter Sizes
NOTE: Somefiltersaremarkedwithan arrowto indicatethe properdirectionof air flowthroughthe filter. The airflow directionwill betowardsthe blower motor.Makesurefilter i
installedcorrectly.
2
21/2
3
31/2
4
5
Nominal Tons
Air Conditioning
Nominal Air Flow
Cubic Feet
per Minute
700-900
900-1100
t100-1300
1300-1500
1500-1700
1900-2100
Recommended Filter Sizes
Sq. In. Surface Arep/Nominal Size
Disposable Filters
400 or 20 x 25
487 or 20 x 30
576 or 14 x 25 (2Req.)
665 or 16 x 25 (2Req.)
753 or 20 x 25 (2 Rea.'_
960 or 20 x 30 (2 Req.'l
Cleanable Filters
246 or 15 x 20
30t or 14x25
356 or 16 x 25
411 or 20 x25
466 or 20 x 25
575 or 24 x 25