Manual

10. Rain Shield Installation
121 Installing The Rain Shield
I
S,ZE.ADHES,VEBAO D.
l_f_SII I IIL_JI I _ PLACEINSIDE
HEATER PLUGS
RAIN SHIELD
connected to an existing system, the ductwork MUST be checked to make
sure it is adequate. Extra runs or larger duct sizes may have to be
installed.
Maximum recommended velocity in trunk ducts is 1000 feet per minute
(5.08m/s). Velocity in branches should not exceed 800 feet per minute
(4.06m/s). Refer to the TechnicalData Label on the unit for unit air volume
requirements and system sizing recommendations.
NOTE: Ductwork sizing affects temperature rise and cooling temperature
differential. Be sure to properly size ductwork to the capacity and airflow
characteristics of your unit. Failure to do so can affect limit controls, com-
pressors, motors, and other components and will lead to premature failure
of components. This will also adversely affect day to day unit perfor-
mance.
Flexible Duct Kits are available from your supplier to effect proper sizing
and installation to Mobile Homes and other standard construction..
Refer to unit rating plate for proper Electric Heat Accessory sizing and see
the Temperature Rise Check section inthe Electric H eat Accessory Instal-
lation Section of this manual.
1. Removeallscrewsfromthe cover plateon Blower/ElectricalAccess Panel.
2. Install adhesive backed gasket on Blower/Electrical Access Panel.
3.Install lower frame of rain shield with 4 screws.
Ductwork Insulation
It is recommended that ductwork installed outdoors have a minimum of 2"
(51mm) of fiberglass insulation and be covered by a weatherproof vapor
barrier that is protected against damage. Caulking and flashings, or other
means adequate to provide a permanent weather seal, must be used.
4.Install rain shield hinged cover with 4 screws.
5. Install circuit breaker filler plates (2 each per unused breaker slot.)
It is recommended that ductwork installed in attics or other areas exposed
to outdoor temperatures have a minimum of 2" (51mm) fiberglass insula-
tion and have an indoor type vapor barrier.
6. Re-install Blower/Electrical Access Panel.
NOTE: VERIFY ALL APPROPRIATE SEALS ARE IN PLACE. SEE
FIGURE 12,
Ductwork Connections
The use of flexible, non-combustible connectors between main trunk
ducts and supply and return air plenums is recommended to minimize
vibration transmission.
11. Air Distribution System
For airflow data (blower performance data, blower speed tap settings,
etc.) see the Technical Data Sheet attached to the unit..
Ductwork
NOTE: Connect supply and return air plenums to unit in a manner that will
allow the top of the unit to be removed without removing plenums. Ple-
nums MUST be individually sealed to unit casing. Ducts MUST be termi-
nated inside structure.
Filters
NOTE: The total heat gain of the structu reto be conditioned as expressed
in total Btu/hr should be calculated by manufacturer's method or in accor-
dance with "A.S.H.R.A.E. Guide" or "Manual J - Load Calculations" pub-
lished by the Air Conditioning Contractors of America. The total heat gain
calculated should be equal to or less than the cooling capacity output
based on D.O.E. test procedures, steady state efficiency times input.
Ductwork, supply registers, and return air grilles MUST be designed and
sized to handle the unit's cooling air volume requirements. If the unit is
All return air MUST pass through a field supplied filter before entering the
unit. If used, an electronic air cleaner MUST be installed in the return air
ductwork. Minimum recommended filter areas are listed in FIGURE 13
and are based on a velocity of 300 ft/min (1.2m/s) for disposable filters
and 500 ft/min (2.54m/s) for washable high velocity filters.
CAUTION
Do NOT operate the unit without all filters in place.
FIGURE 13 Recommended Filter Sizes
NOTE: Some filters are marked with an arrow to indicate the proper direction of air flow through the filter. The air flow direction will be towards
the blower motor. Make sure filter is installed correctly.
Nominal Tons
Air Conditioning
2
2 1/2
3
3 1/2
4
5
Nominal Air Flow
Cubic Feet
per Minute
700-900
900-1100
1100-1300
1300-1500
1500-1700
1900-2100
15
Recommended Filter Sizes
Sq. In. Surface Area/Nominal Size
Disposable Filters
400 or 20 x 25
487 or 20 x 30
576 or 14 x 25 (2Req.)
665 or 16 x 25 (2Req.)
753 or 20 x 25 (2 Req.)
960 or 20 x 30 (2 Req.)
Cleanable Filters
246 or 15 x 20
301 or14x25
356 or16x25
411 or 20 x25
466 or 20 x 25
575 or 24 x 25
427 01 1004 01