Installation Instructions I DIRECT DRIVE BLOWER PH55/PYPA SERIES THREE PHASE SINGLE _) PACKAGE HEAT PUMPS HEAT ELECTRIC c (OPTIONAL) TABLEOF CONTENTS 1, SAFETY LABELING AND SIGNAL WORDS .................... 2 2. UNITDIMENSIONS ...................................... 2 3, SAFE INSTALLATIONREQUIREMENTS....................... 2 4. LOCATINGTHE UNIT .................................... 2 5, UNITELECTRICAL WIRING ................................ 4 Printed in U.S.A. 6.
1. Safety Labeling and Signal Words Danger, Warning and Caution The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING and CAUTION wil! be used on product labels and throughout this manual and other manuals that may apply to the product. 2. Dimensions NOTE: DUCTCOLLARSATTACHEDTO SUPPLYANDRETURNMUSTBE REVERSEDAT INSTALLATION.SEEINSTRUCTIONSON PAGE3.
Minimum Clearances to Combustible Construction SERVICE Blower ACCESS Access CLEARANCES Panel Side ................... 30" (762mm) Electrical Access Panel Side ................. OPERATIONAL CLEARANCES Combustible 30" (762mm) Base (Wood or Class roof covering A, B or C material) Supply and Return Air Ducts Duct Connection Side .................... 0" ........................... 0" .......................................
Condensate Drain Ground Connections The condensate PVC connection A ground lug is installed on the control plate (or electric heat mounting plate) for the ground connection. Use a copper conductor of the appropriate size from the unit to a grounded connection in the electrical service panel or to a properly driven and electrically grounded ground rod. See warning on this page. evaporator drain outlet is a 3/4" (19.
Final Electrical Check Field Installed Equipment Wiring to be done in the field between the unit and other devices, or between separate devices which are field installed and located, MUST NOT exceed the temperature limitations for type T wire and MUST be installed according to the manufacturer's instructions for the devices. FIGURE 5 Make a final wiring check to be sure system is correctly wired.
. Electric Heat Installation General Information FIGURE 8 Electric Heat Accessory Adjusting Thermostat Anticipator Set the heat anticipator of the thermostat instructions provided with the thermostat justment. Model Number AMMH10AHB AMMH15AHB to the proper value. See before making this ad- Anticipator .36 .36 Setting :Z_ ii i ;;;_ Limit Controls The limit controls 9! t; b>:!!_ are mounted on the face of the heater wired into the supply wires to each element.
1. Shut OFF electric power at unit disconnect or service panel. 5. Connect the black wire with terminal 2. Install the appropriate field supplied conduit fitting into the heater knockout located in the rear panel of the unit. The knockout is sized 11/4" in diameter. 6. Connect the red wire with terminal to the loose 3. Connect field installed on the heater mounting copper plate.
7. Air Distribution For airflow data (blower tings, etc.) System performance see the Technical Data data, blower Sheet speed tap set- attached to the unit.. Refer to unit rating plate for proper It is recommended The total heat gain of the structure expressed in total Btu/hr method or in accordance - Load Calculations" to be conditioned steady as should be calculated by manufacturer's with "A.S.H.R.A.E. Guide" or "Manual published by the Air Conditioning tors of America.
8. Start-up Procedures NOTE: The speed taps that the manufacturer sets from the factory for this product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating. Since the manufacturer cannot establish the static pressure that will be applied to the unit, it is the responsibility of the installing dealer / contractor to select the proper speed taps for the application when the unit is installed. Electrical shock hazard.
3.Inspect theinsideoftheunittobesurethatallwiresarein place and all tools, 4. Replace Defrost Control Time Interval Adjustment etc. are removed. all service access Electrical shock hazard. panels. Turn OFF electric power supply at disconnect switch or service panel before removing any access or service panel from unit. Check the unit's operation as outlined in the following instructions. If any unusual sparking, odors or noises are encountered, shut OFF electric power immediately.
(2) When the heating setpoint has been satisfied ......... : The compressor and condenser fan will de-energize immediately. The indoor blower motor will have a delay off and will de-energize after 30 seconds. NOTE: If the jumper "TEST" off. mode, the board wil! default (2) Defrost Mode:Energized Sensor Closed (1) (R,G,Y) On a call for defrost De-energized (O) Defrost ......... When the defrost sensor closes in the heating mode,there is a 30, 60 or 90 minute delay before the defrost mode begins.
CONNECTION DANGER: ELECTRICAL SHOCK WIRING HAZARD DIAGRAM DISCONNECT USE LADDER POWER COPPER BEFORE CONDUCTORS 208/230v 60HZ /F SERVICING ONLY 3PH _ GND [] LUG DANGER: ELECTRICAL SHOCK HAZARD '£3_I 208/230 LI . WIRING DIAGRAM (OPTIONAL) CRANKCASE DISCONNECT GND VAC, 6B POWER BEFORE SERVICING L2 HZ. 3PH HEATERL_v_/_I_ L3 _J BK 5" i 1.-11 G_D <_< _CAP OEFROST CONTROL (_ > HEATER PKG WHEN USED lira [FM 230V r_ DFC BK RE3: BL {> _ , y IFMC i ELECT.
INTERNATIONAL COMFORT PRODUCTS LIMITED WARRANTY CERTIFICATE For Cooling SAVE THIS CERTIFICATE. province It gives you specific & Heating Products legal rights, and you may also have other rights which may vary from state to state and to province. If your unit needs servicing, contact a qualified dealer or qualified service technician of your choice. When requesting service, please have the model and serial number from each unit in your heating and/or cooling system readily available.
ADDITIONAL TERMS FOR RESIDENTIAL APPLICATIONS ONLY The Additional Terms for the components listed below are in addition to, and subject to, the General Terms on the reverse side of this page. Warranty coverage is limited to parts that fail due to defect in materials or workmanship during the specified term. CENTRAL GAS & OIL FURNACE HEAT EXCHANGERS* Gas Model Series: C9MPV. HgMPV. TgMPV. CgMPT. H9MPT. T9MPT. C9MPD. HgMPD. TgMPD: Limited Lifetime Warranty on heat exchangers.