Manual
1. Safety Labeling and Signal Words
Danger, Warning and Caution
The signal words DANGER, WARNING and CAUTION are used to identify levels of hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate hazard. The signal words WARNING and CAUTION wil! be used on product labels
and throughout this manual and other manuals that may apply to the product.
2. Dimensions
NOTE: DUCTCOLLARSATTACHEDTOSUPPLYANDRETURNMUSTBEREVERSEDAT INSTALLATION.SEEINSTRUCTIONSONPAGE3.
ALL DIMENSIONS IN INCHES
261/2
PRESSURE
PORTS
COIL
ACCESS
PANEL
26 s/4
51 \
CONDENSATE DRAIN
CONNECTION
ROUND FLANGE
WILL 3/8 DIA HOLE**
ACCOMMODATE
14" DIA.
RETURN DUCT
m___
10
3 11/2
41
* ELECTRICAL ACCESS FOR LINE VOLTAGE POWER SUPPLY-ONE FOR UNIT, ONE FOR HEATER
** FOR LOW VOLTAGE WIRING
1/4 DIA.*
1/4 DIA.*
9
_1 1/2
ROUND SHAPED FLANGE WILL
ACCOMMODATE 12" DiA
SUPPLY DUCT
3. Safe Installation Requirements 4. Locating The Unit
Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes or, in the absence of
local codes, with the National Electrical Code
NFPA70-1990 or current edition.
The information contained in this manual is intended
for use by a qualified service technician familiar with
safety procedures and equipped with the proper tools
and test instruments.
Failure to carefully read and follow all instructions in
this manual can result in unit malfunction, property
damage, personal injury and/or death.
The unit is designed for outdoor installation only. Place the unit on
a platform at ground level. The unit may be installed on a concrete
slab of 48" (1219mm) x 48" (1219mm) dimensions. Cement
blocks on a 3" sand footing will also work. The slab or blocks
SHOULD NOT be in contact with any part of the structure. Check
local codes covering zoning, noise, platforms, etc..
If practical avoid locating next to fresh air intakes, vent or bed-
room windows. Noise may carry into the openings and disturb
people inside.
Avoid installations under roof overhangs without guttering. Water
draining from the roof onto the unit could produce excessive
noise, and may cause ice to build up on coil or fan.
Placement of the unit should be in a well drained area or the unit
MUST be supported high enough so runoff will not enter the unit.
Do not locate unit where heat, lint or exhaust fumes wil! be dis-
charged on unit (as from dryer vents.)
• Seal supply and return air ducts.
• Check to see that filters are installed correctly and are the
proper type and size.
NOTE: It is the personal responsibility and obligation of the cus-
tomer to contact a qualified installer to ensure that the installation
is adequate and conforms to governing codes and ordinances.
CAUTION
Do NOT operate unit in a corrosive atmosphere containing
chlorine, fluorine, or any other corrosive chemicals.
Clearances
Minimum clearances, as specified in FIGURE 1, MUST be main-
tained from adjacent structures to provide adequate air circula-
tion and room for service personnel.
While minimum clearances are acceptable for safety reasons,
they may not allow adequate air circulation around the unit for
proper operation. Whenever possible, it is desirable to allow addi-
tional clearance, especially around the condenser inlet and dis-
charge openings.
Do NOT install the unit in a recessed or confined area that will per-
mit discharged air from the condenser to recirculate to the con-
denser inlet.
427 01 1005 00
2