8.4.3 Output Connection
Door Lock (Power Fail Safe) Connection (Door Relay)
1. Connect COM wire of Door Relay, White wire with red stripe to +12V.
2. Connect NC wire of Door Relay, Blue wire with white stripe to (+) wire of Door Lock.
3. Connect GND wire to (-) wire of Door Lock.
Door Lock (Power Fail Secure) Connection (Door Relay)
1. Connect COM wire of Door Relay, Gray wire with Red stripe to +12V.
2. Connect NO wire of Door Relay, White wire with Red stripe to (+) wire of Door Lock.
3. Connect GND wire to (-) wire of Door Lock.
Alarm Device Connection (Alarm Relay)
1. Connect COM wire of Alarm Relay and White wire to +12V.
2. Connect NO wire of Alarm Relay, Purple wire to (+) wire of Alarm device.
3. Connect GND port to (-) wire of Alarm device.
Figure: Door Lock, Alarm Device Connection
CAUTION: You should connect REVERSE DIODES as shown in the
picture above. A desirable DIODE is a Fast Recovery DIODE
(current=min. 1A), 1N4004 - 1N4505 or similar.
8.4.4 External Reader Connection
Proximity Reader Connection
1. Connect (+) wire of the Proximity Reader to DC +12V.
2. Connect (-) wire of the Proximity Reader to GND.
3. Connect Data-0 wire of the Proximity Reader to Pink wire.
4. Connect Data-1 wire of the Proximity Reader to Cyan wire.