Technical Specifications
#61-025
VoltAware™ Non-Contact Voltage (NCV)Tester
Instruction Sheet
IMPORTANT SAFETY INFORMATION
Read and understand all of the instructions and safety information in these operating instructions before
using this tester.
WARNINGS
To avoid possible electric shock, personal injury or death follow these guidelines:
• Donotuseifgreenlightisnotilluminatingontester.
• Donotuseiftesterappearsdamagedorisnotoperatingproperly.
• Donotusetesterformorethantheratedvoltageonthetester.
• Donotusewithoutthetesterfullyassembled.
• ThistesterwillnotdetectthepresenceofDCvoltage.
• Thistesterwillnotdetectvoltagesatadistance,suchasthroughwalls,metalconduit,or
shielded wire.
• Voltagedetectionmaybeaffectedbyoutletdesign,insulationthickness/type.
• Donotassumethatnovoltageindicationmeansthecircuitisde-energized.
• Voltagesbelow40VACwillnotbedetectedbythe61-025butarestillshockhazards
that can result in injury or death.
• Usethe3PointSafetyMethod.(1)Verifytesteroperationbymeasuringaknownvoltage.(2)Applytestertocircuitundertest.(3)Returnto
the known live voltage again to ensure proper operation.
• Ensureallngersarebehindngerguardwhentestingforvoltage.
• IfthistesterisusedinamannernotspeciedbyIDEAL,protectionprovidedbytheproductmaybeimpaired.
• Complywithlocalandnationalsafetyrequirements,includingtheuseofappropriatepersonalprotectiveequipment.
Features:
TheVoltAware™NCVtesterisusefulforidentifyinghotconductors,ndingbreaksinwiresanddetectingthepresenceofACvoltageatoutlets,
switches, electrical panels, wires and cables.
• 61-025modelindicatespresenceofvoltagefrom40-1000VAC
• Visualindicationofvoltage
• SelectableAudibleindicationofvoltage
• LowBatteryIndicator
• Sleek,compactdesign
Operation:
• TwistthetesterbodytotheOnposition.
• Verifythegreenlightison.
• Verifytesteroperationonaknownvoltagesource.
• PlacethetipofthetesternearanACvoltagesourcetoobtainavoltageindication.
• Voltagepresenceisindicatedbyared,ashinglight.
Selectable On/Off for Audible Beeper:
• ThetesterdefaultstotheaudibleONmode.
• ToturntheaudibleOff,depressthedarkgraybutton.
• ToturntheaudiblebackOn,depressthebuttonagain.
Note:Testermustbeinstandbymodeforbuttontoactivatecircuitry.
Low Battery Indicator:
• Whenthebatteryvoltagedropsbelow2V,thetesterindicatesthelowbatteryconditionby
turning off the green light.
Battery Replacement:
• Withthetesterinthemiddleposition,pullapartthetwocasehalves.
• Replacewith2AAA(LR03)batteries.
• Reverseprocesstore-assembletester.
Maintenance:
Cleanwithadampclothandmilddetergent.Ifthetesteractserratically,orthegreenlightisnoton,
change the batteries.
Service and Replacement Parts:
Therearenouser-serviceableparts.Toinquireaboutserviceinformation,contactIDEAL
INDUSTRIES,INC.at877-201-9005,orvisitourwebsiteatwww.testersandmeters.com.
Specifications:
Voltage Range:
40-1000VAC(61-025)
Frequency Range:
50-500Hz
Operating Environment:
32to122°F(0to51°C)at<95%R.H.
Storage Temp.:
-4to140°F(-20to60°C)at<95%R.H.
Battery:
(2)1.5VAAAbatteries(IECLR03)
Altitude:
9843ft.(3000m)
Dimensions:
6.0”(H)x0.75”(D)[152mm(L)x19mm(D)]
Weight:
1.6oz.(46g)
Safety
ComplieswithUL-61010,EN61010,CatIV-1000V
Equipment protected by double insulation.
InstrumentcomplieswithinsulationovervoltagecategoryIV.CatIVequipmentisdesignedtoprotectagainsttransientsfromprimarysupply
level.Pollutiondegree2inaccordancewithIEC-664.Indooruse
OFF
ON
#6
1
-
025
Cat IV 40-1000VAC
OFF
ON
#
61-025
4
0-1000VAC
N12966