Installation Instructions
5
5
• FindingGroundedSideofLine
(neutral)
Hold one test prod to the ground and touch
the other test prod to each of the line terminals
until one is found that does not give a voltage
indication.Thisisthegroundedsideofthe
line.
ThecontinuityLEDshouldalsolight.
(61-080,61-076)
• CheckingContinuityofCords,Motors,
Appliances, etc. (61-080,61-076)
Remove power source and place tester across
circuittobetested.ContinuityLEDlightsif
resistance is less than 500kΩ.
• LocatingExcessiveLeakagetoGround
(61-080,61-076)
Place tester across the neutral terminal and the
ground.ThesinglecontinuityLEDshouldindi-
cateneutralandgroundareconnected.Ifboth
LEDslight,thereis>5VAC(N-G)indicatinga
high resistance leakage to ground.
Battery Replacement
(61-080,61-076):
• Replacebatterieswhentouchingtheleads
togethernolongerlightsthecontinuityLED.
• Removetestleadsfromtester.
• Carefully,prythetwobatterycapsfromthe
bottom of the case using a screwdriver.
• Replacethebatteries.
• Snapthebatterycapsbackinplaceensuring
the cap is flush with the bottom of the case.
Accessories:
• 61-070Standardtestleads
(61-076,61-065)
• 61-072
Resistor-fused test leads (61-080,61-067)
• C-90Soft-sidedcarryingcase
• 61-010Leathercase
Maintenance:
• Clean the case with a damp cloth and mild
detergent.Donotuseabrasivesorsolvents.
6
Service, and Replacement Parts:
Forreplacementpartsortoinquireaboutservice
informationcontactTechnicalSupport:
1-877-201-9005 or visit our website
www.idealindustries.com.
Specifications:
VACRanges: 120V,240V,480V,600VAC.
VDCRanges: 120V,240V,600VDC
VoltsAccuracy: Relativeindicationonly
Continuity: LEDlightsat<500kΩ
Response time of 100ms.
Frequency: Operatesat25-60Hz
Overload 1000VDC/750VACrms.
protection:
Operating 32°Fto122°F
Environment: (0to50°C)(<70%humidity)
StorageTemp.: -4°Fto140°F(-20to60°C)
(<80%humidity)
Batteries:
Models61-080&61-076only
(4)1.5V(61-201,IECLR44)
BatteryLife: 200hourstypical.
Accessories TestLeads,(4)Batteries,
included: OperatingManual
Dimensions: 7.2”Hx2.4”Wx1.5”D
[183Hx61Wx38D]mm
Weight: 8.0oz(227g)
Safety: UL61010B-1,CATIII-600V
Double Insulation
Instrumenthasbeenevaluatedandcomplies
withinsulationcategoryIII(overvoltage
categoryIII).Pollutiondegree2inaccordance
withIEC-644.Indooruse.
Clamp Meter
10DB