Instructions / Assembly

In-Sure
®
Models 87, 88, & 90
Push-In Wire Connectors
Installation Instructions:
To be sold only with installation instructions.
1. WARNING! Once time use only. Do not reuse.
2. Wiring must comply with all applicable electrical codes.
3. Turn off power before removing or installing connectors.
4. Strip wires ½”.
5. Grip wire firmly and push connector into open port. Use only one conductor per port.
6. Inspect connection to make sure that all conductors are seated in the bottom of the clear
housing.
Listed as a PRESSURE-TYPE wire connector on #20 - #12 AWG solid wire.
Size #18 AWG Stranded, 7 strands
Sizes #16 - #14 AWG Stranded, 19 strands
Any combination.
600 volts maximum on building wire
1,000 volts signs or lighting fixtures
COPPER TO COPPER ONLY
(Do Not Use On Aluminum)
Temp Rating: 105
C
221
F Max
MADE IN JAPAN
Consult IDEAL for a complete table of UL and CSA certified combinations.