PHASE SEQUENCE
AND OPEN PHASE
INDICATOR
#61-520
HOW TO CHECK PHASE SEQUENCE (cont’d)
Fig. 3
IDEAL INDUSTRIES, INC.
Sycamore, IL 60178, U.S.A.
800-435-0705 Customer Assistance
www.idealindustries.com
ND-1714-2
PLEASE READ
CAREFULLY
Misuse and abuse of
these instructions can-
not be prevented by any
printed word and may
cause injury and or
equipment damage.
Please follow these
instructions faithfully and
adhere to all standard
industry safety rules.
Shown Approx.
1/3 Actual Size
WARRANTY STATEMENT
This tester is warranted to the original purchaser against defects in
material and workmanship for two years from the date of purchase.
During this warranty period, IDEAL INDUSTRIES, INC. will, at its
option, replace or repair the defective unit, subject to verification of
the defect or maltifunction. This warranty does not cover fuses, bat-
teries or damage from abouse, neglect, accident, unauthorized repair,
alteration, or unreasonable use of the instrument.
Any implied warranties arising out of the sale of an IDEAL product,
including but limited to implied warranties of merchantebility and fit-
ness for a particular purpose, are limited to the avobe. The manufac-
turer shall not be liable for loss of use of the instrument or other inci-
dental or consequential damages, expenses, or economic loss, or for
any claim or claims for such damage, expenses or economic loss.
State laws vary, so the above limitations or exclusions may not apply
to you. This warranty gives you specific legal right, and you may also
have other rights which vary from state to state.
IDEAL INDUSTRIES INC.
Attention: Repair Dept.
1000 Park Ave.
Sycamore, IL 60178
1
The warranty is not applicable if the instrument has been misused,
abused, subjected to loads in excess of specifications, has had unau-
thorized repair or has been improperly assembled or used.
6. If the rotation of the disc is
COUNTER-CLOCKWISE
,release
'ON' button and transpose (interchange) the connections of any
two clips to the lines.
7.
Press the 'ON' button again, making certain that all 3 lamps are lit
(no open phases), and check direction of the rotating disc, which
will be
CLOCKWISE .
Release 'ON' button at end of test.
5. If all 3 lamps are lit, check the direction of the
rotating disc on the front panel. If it is in a
CLOCKWISE direction , the Phase Se-
quence is R, S, and T, in order of the lines
where the Red, White and Blue clips are con-
nected.
Release the
'ON' button at conclusion of test.