X6
XA
XW
XN
SEMI
ø22 XW Series Emergency Stop Switches
Instructions
Contact Bounce
When the button is reset by pulling or turning, the NC main contacts
will bounce. When pressing the button, the NO monitor contacts will
bounce.
When designing a control circuit, take the contact bounce time into
consideration (reference value: 20 ms).
LED Illuminated Switches
An LED lamp is built into the contact block and cannot be replaced.
Installing the Anti-rotation Ring
HW9Z-RL
Align the side without thread on the operator with TOP mark ing, the
small
marking on the anti-rotation ring, and the recess on the
mounting panel.
TOP Marking
marking on the anti-rotation ring
Without thread
Anti-rotation Ring (HW9Z-RL)
Installing the Nameplate
Align the side without thread on the operator with TOP mark ing, the
projection on the nameplate, and the recess on the mounting panel.
Nameplate or Switch Guard
When anti-rotation is not required, remove the projection from the
nameplate or switch guard using pliers.
Switch Guard
Projections
Nameplate
Handling
Do not expose the switch to excessive shocks and vibra tions, other-
wise the switch may be deformed or damaged, causing malfunction or
operation failure.