Datasheet

HW Series Emergency Stop Switches
ø22
Contact Ratings
Contact
Block
Rated Insulation Voltage 600V
Rated Thermal Current 10A
Contact Ratings by Utilization Category
IEC 60947-5-1
AC-15 (A600)
DC-13
Characteristics
Contact Ratings by Utilization Category
Operational Voltage 24V 48V 50V
110V
220V
440V
Operational Current
AC
50/60
Hz
AC-12 Control of
resistive loads and
solid state loads
10A 10A 10A 6A 2A
AC-15 Control of
electromagnetic
loads (> 72 VA)
10A 7A 5A 3A 1A
DC
DC-12 Control of
resistive loads and
solid state loads
8A 4A
2.2A 1.1A
DC-13 Control of
electromagnets
4A 2A
1.1A 0.6A
Specications
Operating Temperature –25 to +60°C (no freezing)
Storage Temperature –40 to +80°C
Operating Humidity 45 to 85% RH (no condensation)
Operating Force 50N
Minimum Force Required
for Direct Opening Action
5.5 mm
Maximum Operator
Stroke
10 mm
Contact Resistance
50 mΩ maximum (initial value)
Insulation Resistance
100 MΩ minimum (500V DC megger)
Dielectric Strength
Between live and dead metal parts
Between terminals of different poles
Between terminals of the same pole
2,500V AC, 1 minute
Vibration Resistance
Damage limits: 30 Hz,
amplitude 1.5 mm
Operating extremes: 5 to 55 Hz,
amplitude 0.5 mm
Shock Resistance
Damage limits: 1000 m/s
2
Operating extremes: 100 m/s
2
Operating Frequency 900 operations/h
Life
Mechanical:
500,000 operations minimum
(push-pull: 250,000 operations)
Electrical:
500,000 operations minimum
(push-pull: 250,000 operations)
(at 900 operations/h, duty ratio 40%)
Degree of Protection IP65 (IEC 60529)
Terminal Style M3.5 screw
Weight
76g (HW1B-V322)
99g (HW1B-X422R)
54g (HW1B-Y202)
79g (HW1B-V422R-EMO)
Pushlock Turn Reset Switches (with Removable Contact Block)
Shape Contact Part No. Button Color
ø29mm Mushroom Pushlock Turn Reset
HW1B-V3
1NC
HW1B-V301
Specify a button color code in
place of in the Part No.
R: red
Y: yellow
1NO-1NC
HW1B-V311
2NC
HW1B-V302
2NO-2NC
HW1B-V322
ø40mm Mushroom Pushlock Turn Reset
HW1B-V4
1NC
HW1B-V401
1NO-1NC
HW1B-V411
2NC
HW1B-V402
2NO-2NC
HW1B-V422
ø60mm Mushroom Pushlock Turn Reset
HW1B-V5
1NC
HW1B-V501
1NO-1NC
HW1B-V51
2NC
HW1B-V502
2NO-2NC
HW1B-V522
Yellow buttons cannot be used as emergency stop switches in compliance with EN standards.
When pressed, the button is held depressed. The button is released by turning clockwise.
Pushlock turn reset switches with one or three contact blocks contain a dummy block.
Safety lever lock HW9Z-LS is supplied with the switch.
Other contact arrangements and gold-plated silver contacts are also available. See page 35.
Standards
Applicable Standards Mark File No. or Organization
UL508
UL Listing File No. E68961
CSA C22.2 No. 14 File No. LR92374
EN60947-5-5
TÜV Rheinland
EU Low Voltage Directive
GB14048.5 CCC No.2005103050145656
Emergency Stop Switches (w/Removable Contact Block) Specifications
www.apem-idec.eu
D-038