Instruction Manual
17
4.4 Output Specifications
● Relay Output Specifications
■ FT1A-*12RA
Output Delay
No. of Outputs (Terminal No.) 4 (Q0 to Q3)
Output Type 1a contact
Maximum Load Current 10A
Minimum Switching Load 10 mA/5V DC (reference value)
Initial Contact Resistance 100 m max. (1A, 6V DC)
Electrical Life
100,000 operations min. (rated load 1,800
operations/hour)
Mechanical Life
20,000,000 operations min. (no load 18,000
operations/hour)
Rated Load 250V AC/10A, 30V DC/10A
Dielectric
Strength
Between output terminal
and internal circuit
2,300V AC 5mA, 1 minute
Between output terminals
(COMs)
Status Display Device Monitor screen (LCD display)