7.1 Operating Environment
For designed performance and safety of the Touch, do not install the Touch in the following
environments:
Where dust, briny air, or iron particles exist.
Where oil or chemical splashes for a long time.
Where oil mist is filled.
In direct sunlight.
Where strong ultraviolet rays exist.
Where corrosive or combustible gasses exist.
Where the Touch is subjected to shocks or vibrations.
Where condensation occurs due to rapid temperature change.
Where high-voltage or arc-generating equipment (electromagnetic contactors or circuit
protectors) exists in the vicinity.
7.2 Ambient Temperature
Allow sufficient space for ventilation, and install the equipment away from heat sources.
Allow at least 100mm between the Touch and walls or other equipment.
Do not install the Touch where the ambient temperature exceeds the rated operating
ambient temperature range. When mounting the Touch in such locations, provide a
forced air-cooling fan or air-conditioner to keep the ambient temperature within the rated
temperature range.
The Touch is designed to install on a vertical plane so that natural air-cooling is provided.
If you install it using any other orientation, use forced-air cooling, or lower the ambient
operating temperature.
Derating
FT1A-*12RA
When using the Touch at an ambient temperature of 45°C or higher, reduce the output
current of each output terminal as shown in the figure below.
Installed upright in landscape orientation
7 Installation
Output Current
10A
5A
1A
0
Ambient Temperature
45°C 50°C 55°C