Instruction Manual

30
Turn off the power supply before wiring.
Make the wiring as short as possible and run all wires as far away as possible from
high-voltage and large-current cables. Follow all the procedures and precautions when
wiring the Touch.
Separate the Touch power supply wiring from the power lines of I/O devices and motor
equipment.
Ground the functional earth terminal to make sure of correct operation.
Always use ferrules when wiring stranded wire and multiple wires to the terminal block.
Otherwise there is a risk of wires becoming disconnected.
8.1 Power Supply Terminal
Pin assignment is shown in the following table.
Use applicable cables for wiring and recommended ferrules (made by Phoenix Contact)
as follows.
8 Wiring
+ Power supply 24V DC (+24V)
- Power supply 0V (0V)
Functional Earth (FE)
Applicable cable
AWG16 to AWG22
Stripped wire length 7 mm (Solid wire)
Recommended ferrule
AI 0.34-8 TQ (For AWG22)
AI 0.5-8 WH (For AWG20)
AI 0.75-8 GY (For AWG18)
AI 1-8 RD (For AWG18)
AI 1.5-8 BK (For AWG16)
AI-TW N 2×0 5-8 WH (For AWG20, TW N Pressure Terminal)
AI-TW N 2×0.75-8 GY (For AWG18, TW N Pressure Terminal)
(Phoenix Contact)
Tightening Torque
0.5 to 0 6 N
·
m