Instruction Manual

APPLICATION EXAMPLES
7-4 FC5A MicroSmart PID Module User’s Manual FC9Y-B1283
4. Control CH0 Parameters
Configure the Control CH0 parameters in the PID Module Configuration dialog box. To open Control
CH0 Parameters in the PID Module Configuration dialog box, click on Control Parameters (CH0)
button or Control (CH0) tab.
PID Module Configuration Dialog Box (Control CH0 Parameters)
Item
Setting
(1)
Set Point (SP)
200°C
(2)
AT Bias
20°C
5. Input CH1 Parameters
Configure the Input CH1 parameters in the PID Module Configuration dialog box. To open Input CH1
Parameters in the PID Module Configuration dialog box, click on Input Parameters (CH1) button or
Input (CH1) tab.
PID Module Configuration Dialog Box (Input CH1 Parameters)
Item
Setting
(1)
Input Range
Type K thermocouple, Celsius
(2)
Set Point (SP) Upper Limit
1370°C
(3)
Set Point (SP) Lower Limit
-200°C
(4)
Alarm 1 Type
Upper limit alarm
(5)
Alarm 1 Value
5°C
(1)
(2)
(3)
(4)
(5)
(1)
(2)