CONFIGURING PID MODULE USING WINDLDR
6-10 FC5A MicroSmart PID Module User’s Manual FC9Y-B1283
Input Range
Each input setting range is described.
Input Type and Range
Unit
Range
00h
Type K Thermocouple
Celsius
-200 to 1370°C
01h
Type K Thermocouple with Decimal Point
-200.0 to 400.0°C
02h
Type J Thermocouple
-200 to 1000°C
03h
Type R Thermocouple
0 to 1760°C
04h
Type S Thermocouple
0 to 1760°C
05h
Type B Thermocouple
0 to 1820°C
06h
Type E Thermocouple
-200 to 800°C
07h
Type T Thermocouple with Decimal Point
-200.0 to 400.0°C
08h
Type N Thermocouple
-200 to 1300°C
09h
P L-II
0 to 1390°C
0Ah
C (W/Re5-26)
0 to 2315°C
0Bh
Pt100 with Decimal Point
-200.0 to 850.0°C
0Ch
JPt100 with Decimal Point
-200.0 to 500.0°C
0Dh
Pt100
-200 to 850°C
0Eh
JPt100
-200 to 500°C
0Fh
Type K Thermocouple
Fahrenheit
-328 to 2498°F
10h
Type K Thermocouple with Decimal Point
-328.0 to 752.0°F
11h
Type J Thermocouple
-328 to 1832°F
12h
Type R Thermocouple
32 to 3200°F
13h
Type S Thermocouple
32 to 3200°F
14h
Type B Thermocouple
32 to 3308°F
15h
Type E Thermocouple
-328 to 1472°F
16h
Type T Thermocouple with Decimal Point
-328.0 to 752.0°F
17h
Type N Thermocouple
-328 to 2372°F
18h
PL-II
32 to 2534°F
19h
C (W/Re5-26)
32 to 4199°F
1Ah
Pt100 with Decimal Point
-328.0 to 1562.0°F
1Bh
JPt100 with Decimal Point
-328.0 to 932.0°F
1Ch
Pt100
-328 to 1562°F
1Dh
JPt100
-328 to 932°F
1Eh
4 to 20mA DC
-2000 to 10000
1Fh
0 to 20mA DC
-2000 to 10000
20h
0 to 1V DC
-2000 to 10000
21h
0 to 5V DC
-2000 to 10000
22h
1 to 5V DC
-2000 to 10000
23h
0 to 10V DC
-2000 to 10000
Valid Range for Alarm 1 to Alarm 8 Value
The valid range of each alarm type is described in the following table.
*1: When input is voltage/current, full scale is the linear conversion span.
*2: When input is voltage/current, the valid range is the linear conversion minimum value to linear conversion maximum
value.
Alarm Type
Valid Range
Upper Limit Alarm
(Full scale) to full scale *1
Lower Limit Alarm
(Full scale) to full scale *1
Upper/Lower Limits Alarm
0 to full scale *1
Upper/Lower Limit Range Alarm
0 to full scale *1
Process High Alarm
Input range lower limit to input range upper limit *2
Process Low Alarm
Input range lower limit to input range upper limit *2
Upper Limit Alarm with Standby
(Full scale) to full scale *1
Lower Limit Alarm with Standby
(Full scale) to full scale *1
Upper/Lower Limits Alarm with Standby
0 to full scale *1