User Manual

MorphoAccess® Sigma Series Installation Guide
Section 4 :
Electrical Interface
SSE-00000XXXXX-01
MORPHO DOCUMENT REPRODUCTION AND DISCLOSURE FORBIDDEN
35
September 2013
Output Relay
Figure 13: Output relay wiring
D
1
Relay 1
Contact relay (normally open)
2
Relay 2
Contact relay strip
Nominal characteristics of relay
Load characteristics:
1 A max @ 30 VDC (according to the safety extra low voltage requirements
independently of the power supply),
Resistive load or inductive load; see warning information hereafter for inductive
load.
Inductive load management requires a parallel diode for a better contact
lifetime.
Example of connection for electrical door locks
Figure 14: Example of electric latch connection
1
6
1
6
1
6
1
6
A B C D
+
VCC <30V
Imax < 2A
Electric
door lock
Overswing
diode
MorphoAccess®
SIGMA Terminal
Button on other
side of the door
Relay
Pin 1
Relay
Pin 2