Operating Instructions
Bluetooth Mesh adapter
EIO344
11
7.3 Data storage on sensor side via M12 socket with moneo|blue
The IO-Link port offers the following optional functions:
·
Storage of the IO-Link device configuration for automatic recovery (data storage)
·
Device validation for connected IO-Link devices (validation ID)
·
Vendor and device identification for active device validation (Vendor ID / Device ID)
Set the following parameters as requested:
Parameter
Description
Possible values
[Validation / Data
Storage]
Supported IO-Link standard and
behaviour of the IO-
Link master when a
new IO-
Link device is connected to the
port
No check and clear
Note: Device
validation and data
storage
(Chapter
7.3.1)
Type compatible V1.0
device
Type compatible V1.1
device
Type compatible
V1.1 device with
Backup +
Restore
Type compatible V1.1
device with
Restore
[Vendor ID]
ID of the manufacturer that is to be validated
0...65535
Factory setting: 0
[Device ID]
ID of the IO-Link device that is to be
validated
0...16777215
Factory setting: 0
If the parameter values [Vendor ID] or [Device ID] are changed in the online mode, the data memory will
be deleted and a new backup of the parameter values of the connected IO-Link device will be created in
the IO-Link master.
►
Save changed values on the device.
7.3.1
Note: Device validation and data storage
The user can choose how the IO-Link ports are to behave with regard to the device validation and the storage /
recovery of parameter data of the connected IO-Link device.
The following options are available:
Option
Validation of the IO
-
Link device
Storage of the parameter values
Recovery of the
parameter values
[No check and
clear]
no
no
no
[Type
compatible
V1.0 device]
yes, check the compatibility
with IO
-Link standard V1.0
no
no
[Type
compatible
V1.1 device]
yes, check the compatibility
with IO
-Link standard V1.1
no
no
[Type
compatible
V1.1 device
with B
ackup +
Restore]
yes, check the compatibility
with IO
-
Link standard V1.1 and
uniformity of construction
(vendor ID and device ID)
yes, automatic storage of the
parameter values; changes of
the current parameter values
will be stored
yes, recovery of the parameter
values when connecting an
identical IO
-Link device with
factory settings
[Type
compatible
V1.1 device
with Restore]
yes, check the compatibility
with IO
-
Link standard V1.1 and
uniformity of
construction
(vendor ID and device ID)
no, there is no automatic
storage; changes of the
current parameter values will
not be stored
yes, recovery of the parameter
values when connecting an
identical IO
-Link device with
factory settings
DE