Operating Instructions
EIO344
Bluetooth Mesh adapter
8
5.1 Mounting the connector
To achieve the protection rating indicated in the data sheet, the following has to be observed:
►
Use IO-Link cable with IP class.
►
Connect the connector with the unit. The arrow indicates the position of the coding.
►
Tighten the coupling nut.
• Minimum tightening torque: 0.6 Nm (tightening by hand)
• Maximum tightening torque: 1.5 Nm (using a torque wrench).
5.2 Removing the connector
►
Loosen the coupling nut and simultaneously press the connector against the unit.
5.3 UL application area
For use in the USA and Canada:
►
For connecting the unit and the IO-Link sensor, use UL-certified cables of category CYJV
2/7/8 having suitable ratings.
5.4 Cable length
• Maximum cable length on the input and output side (IO-Link): 20 m.
• Maximum cable length on the output side (analogue signal): no recommendation, depending on
the receiver.
►
Provide all input and output side cables with a strain relief approx. 200 mm behind
the connectors.