Users Manual Part 2
Table Of Contents
- Contents
- 1 Preliminary note
- 2 Safety instructions
- 3 Intended use
- 4 Items supplied
- 5 Function
- 6 Mounting
- 7 Electrical connection
- 8 Parameter setting
- 9 Operation
- 10 Troubleshooting
- 10.1 Troubleshooting incorrect level readings
- 10.1.1 Level too high / too low
- 10.1.2 Measured value is stuck
- 10.1.3 Measured value drops when level close to antenna
- 10.1.4 Measured value fluctuates
- 10.1.5 Measured value is occasionally unstable
- 10.1.6 Lagging of measured value during rapid level changes
- 10.1.7 Measured value correct at 0% (4 mA) but incorrect at 100% (20 mA)
- 10.1.8 Incorrect measured value when level is above 50%
- 10.1.9 Measured value drops to zero close to tank bottom
- 10.1.10 Level measurement is lost in an empty tank
- 10.1.11 Alert mode when level close to tank bottom
- 10.1 Troubleshooting incorrect level readings
- 11 Maintenance, repair and disposal
- 12 Factory setting
- 13 Appendix
Electronic level sensor LW2720
23
6.9.3 Mount the unit with VARIVENT® adapter
u Make sure that the O-ring is mounted in the groove of the unit.
u Screw the VARIVENT adapter onto the unit (not shown). Tighten to the recommended torque (Ò
Installation instructions of the adapter).
u Mount a suitable gasket at the bottom of the VARIVENT adapter.
u Lower the unit with the mounted VARIVENT adapter onto the tank
nozzle.
u Tighten the clamp to the recommended torque
(Ò Manufacturer’s installation instructions).
6.9.4 Install the weld-in adapter on the unit
39 mm
u Make sure that the O-ring is mounted in the groove of the unit.
u Screw the unit into the weld-in adapter.
u Recommended tightening torque: 35 Nm.
6.9.5 Mount the unit with G1 connection
Only for non-hygienic applications (e.g. secondary applications).
GB