LW2720 Electronic level sensor
24
2
1
u Remove the O-ring (1) from the unit before mounting.
Otherwise, the O-ring may come off due to the missing end stop and
enter the process. In this case, the seal is formed by the rear flat seal
(2) (non-hygienic).
39 mm
u Make sure that the rear flat seal (profiled sealing ring) is on the unit.
u Screw the unit into the adapter.
u Recommended tightening torque: 35 Nm.