Users Manual Part 2
Table Of Contents
- Contents
- 1 Preliminary note
- 2 Safety instructions
- 3 Intended use
- 4 Items supplied
- 5 Function
- 6 Mounting
- 7 Electrical connection
- 8 Parameter setting
- 9 Operation
- 10 Troubleshooting
- 10.1 Troubleshooting incorrect level readings
- 10.1.1 Level too high / too low
- 10.1.2 Measured value is stuck
- 10.1.3 Measured value drops when level close to antenna
- 10.1.4 Measured value fluctuates
- 10.1.5 Measured value is occasionally unstable
- 10.1.6 Lagging of measured value during rapid level changes
- 10.1.7 Measured value correct at 0% (4 mA) but incorrect at 100% (20 mA)
- 10.1.8 Incorrect measured value when level is above 50%
- 10.1.9 Measured value drops to zero close to tank bottom
- 10.1.10 Level measurement is lost in an empty tank
- 10.1.11 Alert mode when level close to tank bottom
- 10.1 Troubleshooting incorrect level readings
- 11 Maintenance, repair and disposal
- 12 Factory setting
- 13 Appendix
Electronic level sensor LW2720
31
A
C
E
m
0
mV
0.5
1.0
1.5
2.0
2.5
3.0
0 150 300 450 600 750 900
D
B
Fig.16: Upper blind zone/ detection threshold
A: upper blind zone
B: disturbing echo of object
C: 100% (20 mA) of the analogue range
D: detection threshold
E: medium surface echo
Nozzles or other objects close to the antenna may cause disturbing reflections. Such reflections
can be blocked out by configuring an upper blind zone (A).
Note:
In the upper blind zone, the level is not or not reliably detected.
u Make sure that the maximum level is limited, e.g. by using an overflow or by throttling the inlet.
8.4 System commands
Start simulation Starts the simulation mode. The level set under the parameter [S.Lvl] is
simulated.
Stop simulation Stops the simulation.
Reset to factory settings Restores the factory settings (all parameters)
For further information, please refer to the IODD description www.ifm.com or to the context-specific
parameter descriptions of the used parameter setting software.
8.5 Example parameter setting
• The unit is to monitor the level in an 8 m high tank.
• The unit is mounted in a nozzle (nozzle height: 150mm).
• No tank offset is to be used.
• The medium is aqueous (beer or milk).
• The unit to be used is [m].
• Output OUT2 is to be configured as an analogue output.
u Reset the unit to factory settings:
Execute the system command [Factory reset].
w This serves to avoid incorrect settings and establish a defined start situation.
GB