704287 / 00 09 / 2007 Installation Instructions Inductive sensor IME flush UK
Function and features This sensor detects metals without contact and indicates their presence by providing a switched signal. The nominal sensing range (Sn) can be seen in the type designation on the type label on the unit; operating distance (Sa) 0 ... 0,81 x Sn; (values based on standard measurement with mild steel; a shorter sensing range for other metals). Installation Screw the proximity switch to a firm base. If there is high mechanical stress, ensure that it cannot work loose. Flush mountable (fig.
Electrical connection Disconnect power before connecting the sensor. Open the sensor (fig. 6); connect cable in accordance with the instructions on the type label. Note: insert a miniature fuse according to the technical data sheet, if specified. Recommendation: check the unit for reliable function after a short cirucit. Programming of the output function: Units which are not programmed by means of connections are provided in N.O. Open the wire link for programming the N.C. function (fig. 7A).