3 Installation
Using process adapters the unit can be adapted to different process connections�
Adapters have to be ordered separately as accessories�
A correct fit of the unit and ingress resistance of the connection are only
ensured using ifm adapters�
For small flow rates ifm adapter blocks are available�
3.1 Installation location
General

The sensor tip is to be completely sur-
rounded by the medium�
Insertion depth of the sensor: minimum
12 mm�
Recommended
For horizontal pipes: mounting from
the side�
For vertical pipes: mounting in the rising
pipe�
Conditional
Horizontal pipe /mounting from the bot-
tom: if the pipe is free from build-up�
Horizontal pipe /mounting from the
top: if the pipe is completely filled with
medium�
To avoid
The sensor tip must not be in contact
with the pipe wall�
Do not mount in downpipes that are
open at the bottom!