Drawing

4730 Madison Road, Cincinnati, Ohio 45227-1426 Phone 513 533-6200 Fax 513 871-4084 Web site www.ilsco.com
Canada 1050 Lakeshore Road East, Mississauga, Ontario, Canada L5E1E4 Phone 905 274-2341 Fax 905 274-8763
51
Catalog Figure Wire Range Main Main Dimensions - in. (mm) Die Index
Number Number Main Tap Rebar Ground Rod A B C Number
GGC-1 1 2str-6sol 2str-6sol - - 1.40 (35.6) .75 (19.1) .33 (8.4) O
GGC-2 1 250kcmil-1/0str 2str-4sol #3-4 1/2 - 5/8 2.10 (53.3) .75 (19.1) .33 (8.4) 997
1/2 - 5/8 Rod
GGC-3 1 250kcmil-1/0str 2/0str-1/0str #3-4 1/2 - 5/8 2.10 (53.3) .75 (19.1) .44 (11.2) 997
1/2 - 5/8 Rod
GGC-4 1 250kcmil-1/0str 250kcmil-3/0str #3-4 1/2 - 5/8 2.10 (53.3) .75 (19.1) .61 (15.5) 997
1/2 - 5/8 Rod
GGC-5 1 500kcmil-250kcmil 2str-4sol #5-6 5/8 - 3/4 2.60 (66.0) .75 (19.1) .33 (8.4) 998
5/8 - 3/4 Rod
GGC-6 1 500kcmil-250kcmil 2/0str-1/0str #5-6 5/8 - 3/4 2.60 (66.0) .75 (19.1) .44 (11.2) 998
5/8 - 3/4 Rod
GGC-7 1 500kcmil-250kcmil 250kcmil-3/0str #5-6 5/8 - 3/4 2.60 (66.0) .75 (19.1) .61 (15.5) 998
5/8 - 3/4 Rod
GGC-8 1 500kcmil-250kcmil 500kcmil-350kcmil #5-6 5/8 - 3/4 2.90 (73.7) .75 (19.1) .84 (21.3) 999/1011
5/8 - 3/4 Rod
GGC-9 2 250kcmil-1/0str 6str-8sol #3-4 1/2 - 5/8 2.60 (66.0) .75 (19.1) - 997
1/2 - 5/8 Rod
Compression Grounding
Figure 6 Grounding Grid
TYPE
GGC
Features
Manufactured from high strength copper alloy
Clearly marked with wire size and die index
Range taking
Versatile
Non-hazardous installation
Prefilled with DE-OX
®
oxide inhibiting compound
Temperature Rating 90˚ C
UL Listed and CSA Certified for grounding and bonding
Benefits
Provides maximum conductivity
Provides easy identification and tooling recommendation
Reduces inventory. Eight sizes cover a wire range from 500kcmil to #6,
and 1/2" to 3/4" ground rods.
Can be used as a tap connector or as a lap splice connector
Can be installed in all types of weather with no need for protective
equipment or clothing. Does not produce heat or dangerous particles.
Prevents oxides from forming
Ensures reliability
For direct burial in earth or concrete
667P
L
R
-
5
4
6
5
NOTE: Hydraulic tools required on all sizes except GGC-1 Dieless tools can not be used
All wire sizes, unless noted otherwise, are American Wire Gauge (AWG)
Tested to UL 467, UL File E34440
The GGC Series compression ground tap connector can be used as a tap connector to connect copper ground wire to a copper clad ground rod or as a lap splice connector splic-
ing copper conductors together. The GGC Series of compression connectors are pre-filled with inhibiting compound and are suitable for direct burial.
Notes:
1. ILSCO ILC-12 or ILC-15 Series Tools and ILD Series Dies may be used. Note: Adapter required when using ILC-15 Series Tool. Burndy tools and dies may also be used.
2. Perform a “pre-crimp” on ground rod prior to installing GGC connector. Use an indent type of die such as Burndy’s U2CABT* (Die Index #348).
3. When using #6 AWG solid wire in the tap side, fold conductor double prior to crimping.
4. When using GGC-4, if 3/0
conductor is used in the tap side, use a minimum of 2/0 conductor in the run side.
* U2CABT is a registered trademark TM of Burndy/FCI
TAP
MAIN
Fig. 2Fig. 1