Cut Sheet
C
166
4730 Madison Road, Cincinnati OH 45227-1426 | PH: 513.533.6200 | FAX: 513.871.4084 | www.ilsco.com
In Canada: 1050 Lakeshore Road East, Mississauga, Ontario, Canada L5E 1E4 | PH: 905.274.2341 | FAX: 905.274.8763
High SCCR Conditions
Suitable Overcurrent Protection
Rated Conductors Fuse Required
Dimensions (in.)
Catalog Amps
Conductor Range Per Pole Class/Max Amp Rating
SCCR RMS Volts
Number (CU Wire) Line Load Line Load J T RK1 RK5 G CC SYM Amps Max A B C D E
PDL-11-2/0-3 175 (1) 2/0-14 (1) 2/0-14 (1) 2/0-6 (1) 2/0-6 200 200 200 100 60 30 100,000 600 4.25 3.00 3.05 1.63 2.25
PDL-14-2/0-3 175 (1) 2/0-14 (4) 4-14 (1) 2/0-6 (4) 4-14 200 200 200 100 60 30 100,000 600 4.25 3.00 3.05 1.63 2.25
PDL-16-2/0-3 175 (1) 2/0-14 (6) 4-14 (1) 2/0-6 (6) 4-14 200 200 200 100 60 30 100,000 600 4.25 3.00 3.05 1.63 2.25
PDL-16-400-3 335 (1) 400-6 (6) 2-14 (1) 400-3/0 (6) 2-8 400 400 400 100 60 30 100,000 600 6.00 5.50 3.96 3.25 4.75
PDL-112-600-3 335 (1) 600-2 (12) 4-14 (1) 600-3/0 (12) 4-8 600 600 400 200 60 30 100,000 600 6.00 5.50 3.96 3.25 4.75
PDL-19A-600-3 335 (1) 600-2 (3) 1/0-14 (1) 600-3/0 (9) 1/0-8 600 600 400 200 60 30 100,000 600 6.00 5.50 3.96 3.25 4.75
(6) 2-14
Power Distribution Block
High Short-Circuit Current Rating
Features
•
Manufactured from high strength 6061-T6 aluminum
alloy
•
UL Listed 75˚ C and CSA Certified, 600 volts
•
Electro-tin plated
•
High Short Circuit Rating 100K RMS SYM Amps
•
For use with building code or fine stranded (flexible)
conductor
Benefits
•
Suitable for use with either copper or aluminum conductors
•
Ensures reliability
•
Provides low contact resistance
•
Added protection
All wire sizes, unless noted otherwise, are American Wire Gauge (AWG)
PDL Distribution Blocks are also UL listed with high SCCR ratings with certain Circuit Breaker Combinations - consult factory.
† For further details on conductors, fuse ratings, and additional SCCR ratings please refer to product data sheets.
TYPE
PDL
L
R
-
2
9
6
0
1