O P E QS5 R A T I Vacuum Pump N G M A N U A L
QS5 Operating Manual Thank you for buying the INFICON QS5 Vacuum Pump! QS5 is a high-quality, two-stage rotary vane vacuum pump designed for fast evacuation, deep vacuum, simplified maintenance and durability. With normal use and care as outlined in this manual, your QS5 will provide you with many years of trouble-free operation. The QS5 is a CE approved product and bears the CE mark. Please contact INFICON if you require further information about applicable standards.
QS5 Operating Manual Table Of Contents 1.0 The QS5’s High Performance Features. . . . . . . . . . . . . 2 2.0 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3.0 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 4.0 Identification Of Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . 4 5.0 Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.0 Using the Gas Ballast . . . . . . . . . . . . . . . .
QS5 Operating Manual 1.0 The QS5’s High Performance Features High vacuum, high speed pump Two-stage rotary-vane design provides deep, 15 micron ultimate vacuum and reduces evacuation time. Internal oil pumping design Internal oil pump lubricates the pump chamber and bearings. Anti-backflow design Anti-backflow on the inlet prevents oil from re-entering the system in the event of a power failure, maintaining system purity.
QS5 Operating Manual 2.0 Specifications Frequency 50 Hz 60 Hz Flow (CFM) 4.5 5.0 Flow (L/min) 127 142 Motor ½ HP Inlet 3/8 in & 1/4 in Oil capacity 12.5 oz / 370 mL Net weight 23.5 lb / 10.6 kg 3.0 Safety Precautions Read this manual and become familiar with the specifications of this machine prior to use. Before operating, be sure the power supply conversion switch is set to the appropriate voltage (110V or 220V) for the power source being used.
QS5 Operating Manual The exhaust gas from the vacuum pump is composed of oil and gases from within the pump. The exhaust gas will be hot and should be well ventilated. Never operate the pump with a blocked or restricted exhaust. The resulting back pressure may blow out the sight glass or otherwise damage the pump. The QS5 has been designed to operate most efficiently on high viscosity vacuum pump oil. Other vacuum pump oil may work, but performance results may not be as stated.
QS5 Operating Manual 5.0 Start-up Procedure THE QS5 IS NOT SHIPPED WITH OIL IN ITS RESERVOIR. DO NOT START PUMP WITHOUT ADDING OIL! USE ONLY HIGH VISCOSITY VACUUM PUMP OIL, SUCH AS INFICON PART NUMBER 071-0730! 1 Place pump on flat surface. Remove oil fill cap. A coin or large flat-head screwdriver may be required. 2 Pour oil slowly to avoid over-filling and spilling. Fill to the line indicated on the oil box. NOTE: Oil level will rise when the pump warms up and reaches its operating temperature.
QS5 Operating Manual IT IS IMPORTANT THAT THE PUMP HAS REACHED ITS NORMAL OPERATIONING TEMPERATURE (50°C-70°C / 122°F-158°F) BEFORE ANY CONDENSABLE VAPORS ARE PUMPED. FAILURE TO DO THIS MAY CONTAMINATE THE OIL AND DAMAGE THE PUMP. 10 The QS5 is now ready to evacuate air conditioning and refrigeration systems. UNDER NO CIRCUMSTANCES SHOULD THE FITTINGS ON THE VACUUM PUMP BE USED FOR REFRIGERANT TRANSFER, AS DAMAGE WILL OCCUR TO THE VALVE. 6.
QS5 Operating Manual 8.0 Maintenance DISCONNECT QS5 FROM POWER SUPPLY BEFORE CARRYING OUT ANY MAINTENANCE. 8.1 Changing the Oil THE OIL MUST BE CHANGED WHEN CONTAMINATED. Evacuation of most used systems results in some contamination of the oil, causing deposits of sludge which contain water and acids. These substances will corrode your pump. Changing the oil removes damaging substances and will enhance the life of the vacuum pump. For optimum performance, change the oil after each use of the QS5.
QS5 Operating Manual 9.0 Trouble-Shooting Problem Possible Cause Does not achieve good vacuum 1. Loose/open fittings Remedy 1. Make sure all connections are tight, gas 2. Not enough oil ballast & oil fill cap are 3. Dirty/contaminated oil closed and unused inlet is not open. 4. Old/dirty/non-vacuum 2. Add oil to level indicated rated hoses 3. Change oil 5. Gas ballast open in deep vacuum operation 4. Use new hoses rated for 6. Pump has reached the deep vacuum end of its useful life 5.
QS5 Operating Manual 10.0 Warranty For technical and customer assistance, please call 1-800-344-3304. Do not return pump to INFICON. Contact your local distributor if necessary. INFICON warrants the QS5 vacuum pump to be free from defects of materials or workmanship for a period of two (2) years from the date of purchase. INFICON does not warrant any machine that has been subjected to misuse, neglect, accident or repaired or altered by anyone other than INFICON.
TWO TECHNOLOGY PLACE EAST SYRACUSE, NY 13057-9714 USA Phone: 1-800-344-3304 Fax: 315-434-2552 E-Mail: service.tools@inficon.com www.inficonservicetools.