1700,1,0,8:00-120,11:30-100;16:45-180 
A schedule program can be attached the device’s outputs 
by using the following command: 
1030,m,n,ID 
1030: Command ID 
m:  Module number (0 for SCOM-100 main 
unit, 1-8 for DI-42 I/O expansion units) 
n:  Output number (1-4 for SCOM-100 
main unit, 1-2 for DI-42 I/O expansion 
units) 
ID:  Time schedule ID (1-10) 
A device output attached on a schedule ID will operate 
according to the following rules: 
1. On each day the specific daily schedule program 
with the respective ID is followed. 
2. If no specific day (e.g. for Tuesday) program with the 
respective ID exists, the ‘Everyday’ program is 
followed. 
3. If no specific day program and also no ‘Everyday’ 
program with the respective ID exist, the output 
remains off for the whole day. 
4. The output is activated at the next
 switch on time 
stamp. 
The ‘Clear DO configuration’ command can be used to 
remove the time schedule configuration of an output (see 
4.4.8). 
A special command is available for controlling the total 
ON time duration in a day program: 
1701,ID,P 