- Infinite Alarming & remote control unit User Guide SCOM-100
SCOM-100, User guide  36 
4.5 Analog signal alarming 
4.5.1 Analog input configuration 
The SCOM-100 analog inputs can be configured to 
initiate alarm SMS messages when preset alarm limit 
conditions (low & high alarm limits) are met. A user 
configurable scale can be defined to associate an analog 
input signal to physical units. The configuration command 
is: 
1200,m,n,s,SSL,SSH,SCL,SCH,ALL,ALH,u,d 
1200: Command ID 
m:  Module number (0 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units) 
n:   Input number (1-2 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units) 
s:  Input signal name (Text: 0-15 
characters, may include space 
characters) 
SSL:  Raw value reading for scale low (0-
4095) 
SSH:  Raw value reading for scale high (0-
4095) 
SCL:  Scale low in physical units (-100,000 to 
100,000) 
SCH:  Scale high in physical units (-100,000 
to 100,000) 
ALL:  Alarm low limit in physical units 
(Number in the range of SCL to SCH 
with one optional decimal digit. 
Example: ALL = 52.3) 