ALH:  Alarm high limit in physical units 
(number in the range of SCL to SCH 
with one optional decimal digit. 
Example: ALH = 121.5) 
u:  Physical unit (0-15 characters) 
d:  Delay time in seconds (0-65535) 
For example let us explain all the different parameter 
settings to use a 4-20mA, 0-10 bar pressure sensor wired 
on analog input 2 on the main unit (See section 2.4.2). 
The pressure sensor characteristic is shown in the 
diagram below: 
The 4-20mA input signal is converted by the internal A/D 
converter in the digital raw range of 819 to 4095. 