- Infinite Alarming & remote control unit User Guide SCOM-100
SCOM-100, User guide  38 
The following diagram illustrates the conversion 
characteristic: 
The conversion values are given by the formula: 
Raw digital value:=4095 * Ix/20 
Ix: Input current value (mA) 
According to the formula, a 4mA input is converted to: 
Raw digital value=4095*4/20 = 819 
This is the value setting for SSL. 
A 20mA input is converted to a raw reading of 4095. 
This is the value setting for SSH. 
SCOM-100 physical scale values are limited to integer 
values between -100,000 and 100,000. It is reasonable to 
select the physical scale in the range of 0 to 10,000 mBar 
to gain a better resolution. 
The configuration command would then be: 