1200,0,2,Pressure,819,4095,0,10000,2500,
8500,mBar,15 
The low alarm limit is set to 2.5 Bar, the high alarm limit 
to 9.5 Bar. A 15 second delay is also set so that the input 
signal must persist in value and exceed alarm limits (low 
or high) for 15 seconds. If these clauses are met then an 
alarm SMS will be initiated. 
Note: Alarm annunciation is cancelled if the respective 
Scale (low or high) and limit alarm values (low or 
high) are equal. 
4.5.2 Setting alarm message’s texts for analog inputs 
A similar command to the one for digital inputs is 
available to associate low and high alarm events with 
respective SMS messages (1-128 messages, see 4.3.1). 
The configuration command is: 
1201,m,n,ID1,ID2 
1201: Command ID 
m:  Module number (0 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units) 
n:   Input number (1-2 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units) 
ID1:  ID number 0-128 of the message’s text 
for exceeding the low limit 
ID2:  ID number 0-128 of the message’s text 
for exceeding the high limit 
Note: ID1/ID2 value 0 means no message. 