- Infinite Alarming & remote control unit User Guide SCOM-100
SCOM-100, User guide  40 
4.5.3 Clearing the analog input configuration 
Any analog input configuration settings such as alarm, 
naming, messaging and scaling can be cleared using the 
command: 
1210,m,n 
1210: Command ID 
m:  Module number (0 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units) 
n:   Input number (1-2 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units) 
4.5.4 Setting the analog inputs alarm deadband 
A special command is available to configure alarm 
deadband (hysteresis) for all analog inputs. Alarm 
deadband is a small range in the total scale of the input 
signal where alarm states remain indifferent, holding on 
their last value - in order to avoid frequent SMS 
transmissions. 
The Alarm deadband is given as a percent of the total 
scale. 
1800,d 
1800: Command ID 
d:  Alarm deadband value in % up to 5% of 
the total scale (0-5% in 0.1 steps). 
Example: d =2.3% 