- Infinite Alarming & remote control unit User Guide SCOM-100
SCOM-100, User guide  41 
4.6 Special I/O Functions 
4.6.1 ON/OFF and PID control 
Up to four ON/OFF or PID control function blocks are 
available. Each block uses an analog input for measuring 
the process value and a digital output for control. 
Function block configuration 
1250,id,m,n,m1,n1,sp,g,it,dt,ct,h 
1250: Command ID. 
id:  Function block ID (1-4). 
m:  Module number (0 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units). 
n:   Input number (1-2 for SCOM-100 main 
unit, 1-4 for AI-4 expansion units). 
m1:  Module number (0 for SCOM-100 main 
unit, 1-8 for DI-42 I/O expansion units). 
n1:  Output number (1-4 for SCOM-100 
main unit, 1-2 for DI-42 I/O expansion 
units). 
sp:  Set point value in the range of the 
analog input scale. 
g:  ‘Gain’ value (P) between 1 and 100%. 
The block function depends on the 
‘Gain’ value: A zero value selects the 
ON/OFF control function. A non zero 
value selects the PID function. 
it:  ‘Integral time’ (I) value between 1-1000 
sec. A zero value disables the integral 
part (not relevant for ON/OFF control). 