- Infinite Alarming & remote control unit User Guide SCOM-100
SCOM-100, User guide  62 
Cmd  Description  Syntax  Comments 
1201  Set AI Alarm 
Messages 
cmd,m,n,id1,id2  m:0-4, n:1-2 (base) 
or 1-4 (ext), 
id1/id2:0-128 
1210 Clear AI 
Configuration 
cmd,m,n  m:0-4, n:1-2 (base) 
or 1-4 (ext) 
1800  Set analog IN 
deadband 
Cmd,d  D:0-5% of the total 
scale with 0.1 steps 
9.1.5 I/O Functions 
Cmd  Description  Syntax  Comments 
1250 Set ON/OFF 
- PID Control 
Configuration 
cmd,id,m,n,m
1,n1,sp,g,it,dt,
ct,h 
id:1-4, m,n:AI, 
m1,n1:DO, 
sp:-100000-100000, 
g:0.0-100.0, 
it:0-1000 sec, 
dt:0-200 sec, 
ct:1-15 min, 
h:0.0-20.0 % 
1251 Set ON/OFF 
- PID Control 
state 
cmd,id,s id:1-4, s:0-1 
1252 Set PID 
Control DI 
cmd,id,m,n  id:1-4, m:0-8, n:1-4 
1253 Clear PID 
Control DI 
cmd,id id:1-4 