SUBMITTAL DATA INFRASAVE GAS FIRED INFRA-RED HEATERS LUMINOUS SERIES IL PROJECT: ENGINEER: CONTRACTOR: DISTRIBUTOR: INFRASAVE MODEL #: FUEL: APPROVED BY: DATE: APPROVAL #: AP-SECX-CX-02A IL-X SD RL: 2A RD: May 2006 KH
NOTICE: InfraSave reserves the right to make changes to equipment and specifications without obligation or notification. This publication, or parts thereof, may not be reproduced in any form, without prior written consent from InfraSave. Unauthorized use or distribution of this publication is strictly prohibited. InfraSave Mississauga, Ontario, Waynesboro,Georgia, Phone: 1-866-INFRASV (463-7278) Fax: 1-866-724-9265 http://www.infrasave.com e-mail: info@infrasave.
DIAGRAMS AND SPECIFICATIONS: DIMENSION DIAGRAM FOR THE LUMINOUS HEATERS B TABLE 1: DIMENSIONS : MODEL N0. IL IL IL IL IL A 25 37 50 75 100 B 12 5/8” 19 3/4" 27 1/8" 38" 52 3/4" 22 30 38 49 63 3/4” 1/2” 3/8” 15/16” 3/4” C RATING BTU/ HR WEIGHT LBS. 14” 18 1/4” 25 1/2” 36 3/8” 51” 21,500 34,000 50,000 75,000 100,000 22 26 31 38 45 * BTU Inputs: IL-X 37 NG - 34,000 & IL-X 37 LP - 33,000 GAS SUPPLY NATURAL GAS MINIMUM LINE PRESSURE 6” w.c. MAXIMUM LINE PRESSURE 14” w.c. MANIFOLD PRESSURE 5” w.
MOUNTING DIAGRAM FOR COMBINED INTENSITY HEATERS Minimum distance to combustibles A A E F B B D D A C C D Minimum distance to combustibles CLEARANCES TO COMBUSTIBLES CHART : HEATER MODEL NO TOP < A> SIDE < B> END BOTTOM FRONT < E> REAR IL 25 N/L 24” 27” 24” 60” 60” 24” IL 37 N/L 24” 27” 24” 60” 60” 24” IL 50 N/L 24” 27” 24” 78” 78” 24” IL 75 N/L 30” 33” 30” 84” 84” 30” IL 100 N/L 36” 33” 30” 84” 84” 30” SUGGESTED MOUNTING DISTANCES FOR COMFORT:
COMPONENT DESCRIPTION: IGNITION DIRECT SPARK MODULE COMBINATION GAS VALVE 24 VOLT NATURAL GAS 5” W.C. MANIFOLD PRESSURE PROPANE 10” W.C.