17. Click Next.
18. In the new Access Point window, complete the following field entries using the company
specific site template. If the company template overrides defaults listed below, enter them
when updating these fields.
a. In the AP Channel (Numeric 1-38) field, type the channel of this AP from the site-specific
template.
b. In the UL Margin (Numeric 0-15) field, type 2.
c. In the Reuse Code field, type information from the site-specific template.
d. The Broadcast Gold Code field is grayed out on purpose as this field is auto-generated.
e. In the Target Transmit Power (In dBm 4-32) field, type information from the site-
specific template.
f. In the Max Seconds Without Timing (Numeric: 0-1000) field, type 600.
g. In the RPMA Mode field, enter information from the site-specific template.
h. In the Maximum UL PDUs field, type 16.
i. In the Keep Alive Message Interval (Seconds 5-3600) field, type 10.
j. In the Backhaul Message Timeout (Seconds 5-255) field, type 10.
k. In the Max UL Margin (dB 0-31) field, type 20
l. In the UL Overload Alarm Threshold (dB 0-31) field, type 3.
m. In the AP Interference Alarm Threshold (dB 0-31) field, type 10.