displays “AT” alternately (Character: ), the instrument is in self-adjusting status. In
this status, the instrument will execute position adjustment by 2 - 5 times oscillations,
then it will turn out PID control parameter automatically (M50, P and T parameter).
The instrument will return to PID automatic control status at the end of self-
adjustment. If user want to quit in the course of self-adjusting, keep pressing 《”
key for more than 2S, till “AT” character in the SV screen disappears.
Attention: If user wants to use self-adjusting function again after first using, user
needs to set “CtrL” to be “2” to start it (more information please check “Parameter
Setting and Defining”). The parameter values of adjusting control are not the same at
the different setting temperatures, so please execute self-adjustment at the most
common setting value of the system. If the setting values change often, user can
modulate with the median.
7. Parameter Setting and Defining
After power-on, keep pressing the “SET” key for more than 2S to enter setting mode. User
can use ”Keyor“”Keyto set the value. After finishing, press “SET” key to confirm
and enter next function setting. PV/SV screen will be in normal display after setting.
Note: If there are modified operations in setting mode, the instrument will save current
value automatically after no operation for more than 10 seconds, and return to normal
status.
Function Setting
Description
Setting Range
Unit
Remarks
Factory
Default
Code
Name
HIAL
Upper Alarm Limit
-1999+9999
1
9999
LoAL
Lower Alarm Limit
-1999+9999
1
-1999
dHAL
Maximum
Deviation Alarm
09999
1
9999
dLAL
Minimum Deviation
Alarm
09999
1
9999
dF
Hysteresis
0200.0
0.1
0.3
CtrL
Control Output
0ON/OFF
3
1/3PID
2: Self-adjustment
M50
Integral
09999
0.1
0: Cancel
1000
P
Differential
09999
0.01S/
500
t
Hysteresis Time
19999
S
120
Ctl
Control Period
1120
S
4
Sn
Input Sensor
042
Table 1
0