E V O R A D a t a s h e e t P a g e 8 o f 1 0
Load Specifications
Single Gang Installation
The following table provides the load ratings at absolute maximum based on the load type in a single gang wall box.
Actuator Ratings
Voltage Frequency Power / Amperes Load Type
SMPS
120-240Vac 50/60Hz 200mA +12VDC Output
Only
120-240 Vac 50/60 Hz 4.1 A Resistive
120-240 Vac 50/60 Hz 4.1 A General Purpose
120-240 Vac 50/60 Hz 500 W Tungsten / ELV
120-240 Vac 50/60 Hz 250 VA Electric Ballast
Relay Actuator
120 Vac 50/60 Hz 1/10 HP Motor
120 Vac 60 Hz 2.9 A Resistive
120 Vac 60 Hz 500 W Tungsten / ELV
120 Vac 60 Hz 250 VA Electronic Ballast
TRIAC Dimmer
120 Vac 60 Hz 1/10 HP Motor
120 Vac 60 Hz 2.9 A Resistive
120 Vac 60 Hz 2.9 A General Purpose
120 Vac 60 Hz 350 W Tungsten / ELV
MOSFET Dimmer
120 Vac 60 Hz 250 VA Electronic Ballast
120-240 Vac 50/60 Hz 7200VA General Purpose
120-240 Vac 50/60 Hz 960W Tungsten / ELV
120-240 Vac 50/60 Hz 800VA Electronic Ballast
Master Contactor
120-240 Vac 50/60 Hz 30A Resistive
Class-2 Output
The Load Assembly has been designed to provide +12VDC power to devices connected to the S5bus. The Load
Assemblies can operate in parallel to supply a higher total load capacity than that achievable by a single Load
Assembly. However, the total output is derated as per the table below for accommodating the stability of the
power supply circuitry. The total available output power must be shared with the EVORA User Interface. Refer to
the following table for Class-2 Output ratings.
Number of Load
Assemblies
Nominal Voltage Voltage at Maximum
Load
Output Rating
1 +12VDC +11.0VDC 200mA
2 +12VDC +11.0VDC 375mA
3 +12VDC +11.1VDC 550mA
4 +12VDC +11.1VDC 660mA
5 +12VDC +11.2VDC 880mA
6 +12VDC +11.2VDC 990mA