User guide

Page 61
Genesis II Installation Instructions
© Mass Electronics Pty Ltd 2010Chapter 3 – Electrical Installation
END OF
CABLE
JUMPER
RS485
COMMS
CONNECTIONS
POWER
3-4.11 GENII CS REM Control Station Module
The GENII CS REM Control Station Module is powered by 24VAC ±10% @ 50/60Hz. Power Consumption
is 3 VA maximum.
The GENII CS REM mounts into a standard electrical wall plate. The only connections to the GENII
CS REM are 24VAC power and the RS485 Comms link. Locations of electrical terminals are shown in
Figure 3-15, which is a rear view of the module.
When all connections have been made, protect the module from dirt and moisture by covering it with
plastic but do not mount the module in the wall plate until commissioning is completed. This is to
allow addresses to be set as part of the commissioning process.
Figure 3-15:  GENII CS REM Control Station Module