Installation Instructions for Innotech IG04 BACnet Gateway and Vaisala Transmitter / Sensor
Page 20 © Mass Electronics Pty Ltd 2011Edition 5.0 dated 11/11/2013
Ethernet Tab
Under the Ethernet tab you can configure or modify the following settings:
Address type, IP address, Default Router, and Net Mask
HTTP Port Number
Net Comms Port number (Innotech Service Port number)
BACnet Port number
As mentioned previously in the Accessing Embedded Server and FusionLIVE section, your computer
MUST be on the same network range as the IG04 BACnet Gateway in order to access the embedded
web server.
If you change the IP address from the default settings in this step, you will have to modify the IP
address of your computer to be on the same network range as this new IP address. Click on Apply to
save your settings.
If you specify a dierent HTTP Port to the default (80), you will have to specify the port number when
accessing the IG04 BACnet Gateway through a browser. For Example: if the HTTP Port was changed
to 90, you need to enter 192.168.2.100:90 in the web browser to access the IG04 BACnet Gateway.
Figure 18:  Configure IG04 settings in FusionLIVE – Ethernet Tab