Wiring Using The 8-Pin M12 Connector With Independent Cabling For Heating
The wiring example provided below at Figure 1 is recommended for most installations, providing a
separate cabling run of high quality cable for the Vaisala device heating current (if required). The pin
connections for the 8-Pin M12 and wire colours are listed in Table 1 on page 7.
For installations that do require the optional heating accessory, ensure a high capacity cable
between the DC Power supply and the Vaisala device is used.
Figure 1:  Wiring guide for Vaisala device M12 Connector with independent cabling for heating
The 8-Pin M12 connector is located on the bottom of the Vaisala device.
NOTE
The 16mm
2
Copper Cable to Earth Ground cable is a critical component for the correct operation of the surge protector.
Ensure this is installed correctly.
NOTE
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Ethernet
&
BACIP
+
-
SHLD
IG04 Default Settings
IP Address: 192.168.2.100 (Static)
S/M: 255.255.255.0
Innotech Port: 20000
BACnet/IP
BACnet Port: 47808
BACnet Instance: 1509
Baud Rate: 19200
Fault Timeout: 30 Sec
-
+
Isolated DC
Power Supply
Earth Ground
Ethernet
Port &
BACnet/
IP Output
SHLD
EOL
C+
C-
SER Terminal Not Used
(Service Tool Connection)
*
1
Wire WXT520 / WMT52 Device to the
WSP150 Surge Protector in accordance with
appropriate Vaisala technical documentation.
Innotech IG04
BACnet Gateway
BLK Wire (Vin)
RED Wire (Vin+)
24V
0V
Shielded cable length should NOT exceed
3m when connecting WXT520 / WMT52
Device to WSP150 Surge Protector
If a surge protector is not installed, connect the cables directly
RS485 [+]
S
RS485 [-]
RS485 [
Shield
]
RS485 Line
Termination
Jumper
+
-
BLU Wire (RX)
GRY Wire (RX+)
1 2
3
4
5
6
7
8
YEL (Vh+)
PNK (Vh)
RED Wire (Vin)
BRN Wire (Vin+)
*
1
RED Wire (Vh+)
BLK Wire (Vh)
24V to 32V DC
@ < 200mA
*
2
@ < 800mA
*
3
*
2
When heating is NOT used.
*
3
Higher heating currents cause
voltage drop. Select cable with sufficient
cross section for longer runs.
Note: Colour coded as per
Vaisala documentation
GRY Wire (RX+)
BLU Wire (RX)
Vaisala WXT520 Weather Transmitter / WMT52 Ultrasonic Wind Sensor
M12 connector pin-out *
1
WSP150 Surge Protector
*
1
16mm² Copper Cable
HTTP Port: 80
SER
WXT
MSTP
IG04 Default Settings
IP Address 192.168.2.100 (Static)
Subnet Mask 255.255.255.0
HTTP Port 80
Innotech Port 20000
BACnet/IP
BACnet Port 47808
BACnet Instance 1509
Baud Rate 19200
Fault Timeout 30 seconds