User Manual

Accutech reserves the right to substitute comparable components without notice.
R051903
M090503
CUT SHEET: Elevator Deactivation
Elevator Deactivation Circuitry is designed to prevent someone (or an asset) wearing an Accutech Tag from using an elevator
to leave a monitored floor. Using Relays enclosed in the Elevator Deactivation Relay Cabinet, the Elevator Company is able
to interface with the Accutech System.
Therefore:
If a Tag enters a monitored elevator zone, the elevator’s call button on that floor will be deactivated
(Call buttons on other floors are unaffected and no one is restricted from coming to the floor).
When a Tag is in the zone (or approaches the zone) and the elevator doors are open, an alarm will sound and the
elevator doors will remain open.
If the elevator car is en route to the floor when a Tag approaches the zone, the elevator will arrive on the floor, the
door(s) will open, and the system will alarm.
ELECTRICAL:
Operating Voltage: 12V DC
Current Consumption: 120 mA maximum
Contact Rating: 100 mA / 12V DC
Cable: need minimum 22-gauge, 6-conductor
MECHANICAL:
Construction: Metal case
Enclosure size: 7.80” x 8.25” x 3.75”
Enclosure weight: 3.5 US pounds
OPERATING CHARACTERISITICS:
Dry Contacts supplied by Elevator Company for
door switch
12V DC Alarm Voltage energizes K1 Relay to
deactivate the Car when a Tag is detected and the
elevator door is open.
12V DC Tag Detect Voltage energizes K2 Relay
to deactivate the Call Button when a Tag is
detected.
ENVIRONMENTAL:
Operating Temperature: 32º to 120º Fahrenheit
Intended for indoor use only.
DUTY CYCLE:
Rated for continuous use.
Elevator Deactivation
Model Number: ED
800-356-2671 | Accutech | www.accutech-ics.com