User's Manual

iv UL Addendum (UL 294, BP9480) Installation Manual
LT, SB, BR, CB
Long Term (LT), Slotted Back (SB), Band Removal (BR), Cut Band (CB)
Tags, small wristwatch sized device, activated Tag sends signal via receiver
to the Controller.
TAD, PTAD
Tag activator/deactivator, also checks Tag’s battery and assists in finding
lost Tags. PTAD is identical to TAD except it does not activate/deactivate
tags. Testing with TAD shall be conducted before use daily.
CL-8A Keypad, used to disable audible device.
Installation - The control units and accessories are intended to be installed in accordance
with the following:
1. The National Electrical Code, ANSI/NFPA 70.
2. Local Authority having Jurisdiction.
3. Manufacturer's installation instructions provided with each unit.
Access Control
1. The minimum system configuration consists of Model ESI, ESRI, TW, keypad, audible
device or magnetic lock or door/elevator deactivator, Tags LT and/or SB and/or BR and
or CB.
2. The system shall be installed in the fail-safe mode and shall release the lock upon loss of
power, loss of connection between ESI and fire alarm control panel. Loss of battery to the
TAG (LT, SB, BR, CB) shall release the lock.
3. The control unit shall be mounted in a protected area.
4. The system does not provide standby power.
5. All accessories are restricted to be installed in the same room. A room is defined as an
enclosed area bounded by walls extending from ceiling to floor, one or more of which
may contain an entranceway that is marked with an Exit sign under the requirements of
the NFPA code. An enclosed area bounded by walls from drop ceiling to floor is not
considered a room but is determined to be part of the room. Rooms having no exit, as
defined under the NFPA that are found within a room with exits, as defined by the NFPA,
are considered part of the overall room.
6. Monitoring station is not UL Listed as an access control unit accessory.
7. This equipment is not evaluated as or meant to be installed as a burglary alarm system.
8. The Model ED is not listed as elevator equipment. The fire alarm control panel shall
override the ED.